{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Ceramic tube set TSC140B085-300/35-Si-1500 74916387

SKU 74916387 Model TSC140B085-300/35-Si-1500 Brand Kromschroder

Photos

no photo yet

Key specifications

Nominal diameter (DN)85 mm
Length300 mm
Construction typeceramic tube set
Country of originGermany
Outlet diameter85 mm
Distance from flange to front edge35 mm
Catalogue article numbers74916387, tsc140b085-300/35-si, 624.517.001
Gas exit velocity80–150 m/s
Turndown ratio1:15
NOx emissionsless than 80
Maximum furnace temperature1450 °C
Installation torqueup to 30
all specifications (12) ↓
2210.53 EUR
2009.57EUR
in stock · 1

incl. 21% VAT · 1660.80 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder ceramic tube set TSC140B085-300/35-Si-1500 (SKU 74916387) is a replacement kit for Kromschroder BIC 140L and BICA 140L gas burners. It includes a silicon carbide ceramic tube with a nominal diameter of 85 mm, a length of 300 mm, and a distance from flange to front edge of 35 mm. The set is designed for high-temperature furnaces up to 1450 °C, with gas exit velocity of 80–150 m/s and turndown ratio of 1:15. It ensures stable combustion with NOx emissions less than 80 mg/kWh. The kit is manufactured in Germany and includes the ceramic tube, sealing cord, screws, and nuts for installation.

Further details

Installation notescross-tightening of the nuts ensures even contact of the ceramic with the flange
Kit Contentsceramic tube + seal + fasteners
Recommended usehigh-temperature ceramic paste to prevent thread seizing
Signs of wearvisual defects: cracks, chips, surface melting, porosity; unstable combustion; burner housing overheating; end of planned service life

Choosing and fitting

Parts of this type are selected by matching the burner model and size, as well as the tube's diameter, length, and head position relative to the furnace flange. Before ordering, verify the nominal diameter, tube length, and distance from flange to front edge against the existing burner specifications. Installation involves mounting the ceramic tube from the furnace lining side, using the provided fasteners and tightening to the recommended torque (up to 30 N·m). Ensure proper alignment with ignition and ionization electrodes if present.

Signs of failure

Failure of ceramic tubes of this kind typically manifests as cracks, chips, surface melting, or porosity. Equipment symptoms include unstable combustion, flame lift-off or detachment, popping during ignition, and overheating of the burner housing due to flame contact with metal parts. Regular inspection for visual defects and monitoring of combustion stability are recommended to detect wear.

Fits equipment

Kromschroder BIC 140L / BICA 140LKromschroder BIC 140LKromschroder BICA 140L

All specifications

Nominal diameter (DN)85 mm
Length300 mm
Construction typeceramic tube set
Country of originGermany
Outlet diameter85 mm
Distance from flange to front edge35 mm
Catalogue article numbers74916387, tsc140b085-300/35-si, 624.517.001
Gas exit velocity80–150 m/s
Turndown ratio1:15
NOx emissionsless than 80
Maximum furnace temperature1450 °C
Installation torqueup to 30

Part numbers

SKU74916387
Additional article624.517.001
ModelTSC140B085-300/35-Si-1500