Honeywell Gas boiler control unit S4565A 2050B
SKU S4565A 2050B
Model S4565A2050
Brand Honeywell
Photos
Key specifications
| Ignition type | Spark ignition (DBI) |
|---|---|
| Safety standard | EN 298, EN 60730-1 |
| Supply voltage | 220–240 V |
| Flame detector type | Flame sensor rod |
| Fuel | Gas |
| Application | Mora W 10-15-25-35-40-50 E boilers |
| Compatible gas valves | vk41 series |
| Flame sensor | flame sensor rod |
| Reset button type | Own or external reset button |
| Reset wait time | 15 s |
| Restart behavior | Repeats starting sequence |
| Safety feature | Flame failure lockout |
| Connector type | Top connector |
| Flame monitoring | Yes |
| Extended ignition time | Preset extended ignition time |
| Direct flame interaction | No |
| Integrated protection | Yes |
| Supported ignition systems | DBI (spark ignition) |
| Combustion type | Atmospheric |
| EN 298 compliance | Yes |
| Control system | CVI |
254.66 EUR
231.51EUR
in stock · 1
incl. 21% VAT · 191.33 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This is a gas boiler control box for atmospheric gas burners. It operates at 220–240 V and uses a flame sensor rod for flame detection. It provides spark ignition (DBI) with a preset extended ignition time and a flame failure lockout. The control system is CVI, and the unit is designed to EN 298 and EN 60730-1. It is intended for Mora W 10-15-25-35-40-50 E boilers and connects to VK41 series gas valves via the top connector.
Further details
| Direct flame interaction | does not affect the flame directly |
|---|---|
| EN 60335 compliance | can be used in installations that meet EN 60335 |
| En 298 Compliance | designed in accordance with EN 298 |
| Extended Ignition Time | ignition device turns off after extended ignition time is over |
| Model Variant | Suffix A: atmospheric system with spark ignition |
| Modifications | Various modifications for different ignition systems |
| Safety Feature | blocked if flame not set within safe ignition time |
Choosing and fitting
Control boxes of this type are selected by supply voltage, ignition system (spark or pilot), and gas valve series. They mount on the gas valve using the top connector and can be oriented within 90° from vertical. Before ordering, confirm the flame sensor type (rod or other) and the reset button configuration. The control box must be compatible with the boiler's gas valve series.
Signs of failure
If the flame does not establish within the safe ignition time, the control box locks out and must be reset. A reset is done with the own or external button; wait at least 15 seconds before retrying. If the flame goes out during operation, the box repeats the starting sequence. Repeated lockouts often point to a faulty flame sensor rod or gas valve connection.
Fits equipment
MORA W 10-15-25-35-40-50 E
Mora W10-15-25-35-40-50 EHoneywell VK41 seriesMora W 10 EMora W 15 EMora W 25 EMora W 35 EMora W 40 EMora W 50 E
All specifications
| Ignition type | Spark ignition (DBI) |
|---|---|
| Safety standard | EN 298, EN 60730-1 |
| Supply voltage | 220–240 V |
| Flame detector type | Flame sensor rod |
| Fuel | Gas |
| Application | Mora W 10-15-25-35-40-50 E boilers |
| Compatible gas valves | vk41 series |
| Flame sensor | flame sensor rod |
| Reset button type | Own or external reset button |
| Reset wait time | 15 s |
| Restart behavior | Repeats starting sequence |
| Safety feature | Flame failure lockout |
| Connector type | Top connector |
| Flame monitoring | Yes |
| Extended ignition time | Preset extended ignition time |
| Direct flame interaction | No |
| Integrated protection | Yes |
| Supported ignition systems | DBI (spark ignition) |
| Combustion type | Atmospheric |
| EN 298 compliance | Yes |
| Control system | CVI |
Part numbers
| SKU | S4565A 2050B |
|---|---|
| Additional article | 534.412.908 |
| Model | S4565A2050 |
| Type designation | S4565A 2092U |