SKU 3013071 Model RMO88.53C2 Brand Riello

Photos

Key specifications

Frequency50–60 Hz
ApplicationRiello burners
Fueloil
Original equipment manufacturerSiemens
Supply voltage220–240 V
Ambient temperature0–40 °C
Maximum length of ionisation/UV cable1 m
Safety time 1, burner/pilot burner start-up tSA15 s
Flame detector typePhotocell
Mounting featurePlug in base
Control featuresAutomatic
Cycle typeintermittent
Safety standardEN267
Design featuresincreased anti-interference capability
Control designmicroprocessor-based
Flame failure responselockout after 3 flame losses
Reset button max pressure10 N
Ion pin to ground minimum resistance50
Burner stage controlone-stage and two-stage
Flame sensor typeIonisation electrode or UV detector
all specifications (20) ↓
271.01 EUR
246.37EUR
in stock · 1

incl. 21% VAT · 203.61 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

This burner control unit (RMO88.53C2) is a microprocessor-based oil burner control for Riello burners, supplied by Siemens. It is designed for 220–240 V, 50–60 Hz, intermittent duty, and meets EN267. It has a 5 s safety time at start-up and a flame detector type of photocell. It accepts an ionisation electrode or UV detector as flame sensor. It provides one-stage and two-stage control, mounts on a plug-in base, and is rated for 0–40 °C ambient. It locks out after three flame losses.

Further details

Component typeBurner control unit / Flame safeguard / Control box
Control functionsPre-purge, ignition spark, gas valve/oil pump control, flame monitoring, safety lockout
Interface compatibilityAir pressure switch and modulation controls
Selection criteriaSupply voltage, safety time, flame sensor type

Choosing and fitting

Controls of this type are selected by supply voltage, safety time and the flame sensor type they accept. Before ordering, verify that the wiring base matches the existing socket and that the timing and reset behaviour suit the burner. During installation, keep the ionisation/UV cable no longer than 1 m, ensure the ion pin-to-ground resistance is at least 50 MΩ, and do not press the reset button with more than 10 N. Disconnect power before rewiring, do not confuse line and neutral, and keep controller terminals well insulated from the ignition cable.

Signs of failure

When flame is lost, this class of control normally attempts a restart; after three flame losses it locks out. Fault, false flame and low-voltage conditions are indicated by the alarm lights. A flame sensor cable longer than 1 m, a contaminated sensor, or an ion-pin-to-ground resistance below 50 MΩ can prevent flame confirmation and lead to lockout. Check the sensor and cable insulation before replacing the control.

Manufacturer documentation

Fits equipment

Riello Riello burnersRiello burnersRiello Riello RL34/1Riello RL44/1Riello RL28/1Riello RL38/1Riello RL34Riello RL44Riello RL28Riello RL38Riello RL50Riello RL64Riello RL70Riello RL100Riello RL130Riello RL190

All specifications

Frequency50–60 Hz
ApplicationRiello burners
Fueloil
Original equipment manufacturerSiemens
Supply voltage220–240 V
Ambient temperature0–40 °C
Maximum length of ionisation/UV cable1 m
Safety time 1, burner/pilot burner start-up tSA15 s
Flame detector typePhotocell
Mounting featurePlug in base
Control featuresAutomatic
Cycle typeintermittent
Safety standardEN267
Design featuresincreased anti-interference capability
Control designmicroprocessor-based
Flame failure responselockout after 3 flame losses
Reset button max pressure10 N
Ion pin to ground minimum resistance50 MΩ
Burner stage controlone-stage and two-stage
Flame sensor typeIonisation electrode or UV detector