Brahma Control box 18049001

SKU 18049001 Brand Brahma

Photos

Key specifications

Safety time5 s
Flame loss reaction timeless than 1 second
Independent safety contacts2 contacts
Firing stagessingle-stage
Cycle typeintermittent (cyclic)
Maximum oil burner throughput30 kg/h
Compatible burnersRiello, Baltur, Weishaupt, Lamborghini
Air supplyforced draft
Flame detection methods supportedionisation, UV, or IR
Pre-purge time20 s
all specifications (10) ↓
157.32 EUR
143.02EUR
in stock · 2

incl. 21% VAT · 118.20 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Brahma 18049001 is a microprocessor-based control box for single-stage forced-draft liquid fuel burners, operating in intermittent (cyclic) mode. It has a pre-purge time of 20 seconds and a safety time of 5 seconds, with a flame loss reaction time of less than 1 second. It supports flame detection via ionisation, UV, or IR methods and includes two safety contacts. It is compatible with burners from Riello, Baltur, Weishaupt, and Lamborghini, and is suitable for oil burners with a maximum throughput of 30 kg/h.

Further details

Applicationboiler equipment, heat generating equipment, industrial installations, specialized equipment
Application Typeautomate ignition, flame monitoring and safe shutdown of liquid fuel burners
Flame Detectorphotocells FC11, FC13, FC14 or FC14L
Fuel Typeliquid fuel (diesel or heavy oil)

Choosing and fitting

When selecting a control box of this type, verify that the supply voltage, safety time, pre-purge time, and flame detection method match the original. Ensure the wiring base or plug connector is compatible, as controls are not interchangeable across different series. Check the burner's specifications and the appliance manual to confirm the required parameters.

Signs of failure

Common failure modes include failure to ignite, lockout after the safety time, or immediate shutdown upon flame loss. The equipment may show a fault code or fail to start. Check the flame detector, wiring connections, and the control box's internal fuse or relay for issues.

All specifications

Safety time5 s
Flame loss reaction timeless than 1 second
Independent safety contacts2 contacts
Firing stagessingle-stage
Cycle typeintermittent (cyclic)
Maximum oil burner throughput30 kg/h
Compatible burnersRiello, Baltur, Weishaupt, Lamborghini
Air supplyforced draft
Flame detection methods supportedionisation, UV, or IR
Pre-purge time20 s

Part numbers

SKU18049001
Additional article246.124.024