| Supply voltage | 12 V |
|---|---|
| Safety time | 10 s |
| Flame detector type | ionisation, UV, photodiode |
| Protection class (IP) | IP00 (with base - IP40) |
| Catalogue article numbers | 18049400, 246.124.152 |
| Installation position | any |
| Fuel | gas, oil, combination |
| Firing stages | single-stage / two-stage |
| Cycle type | intermittent |
| Flame loss reaction time | < 1 second |
| Safety feature | non-volatile lockout with manual reset |
| Service life under maximum load | 250000 |
| Dimensions | 90 x 85 x 65 mm |
| Operating temperatures | -20–70 °C |
| Storage temperature | -40–85 °C |
| Maximum humidity | 95 |
| Independent safety contacts | 2 contacts |
| Base present | no |
| Waiting time | verify on housing label |
| False flame check | yes |
| Automatic self-check | yes |
| Lockout alarm output | yes |
| Remote control | yes |
| LED indicators | multicolour LED |
| Built-in ignition transformer | yes |
| Sensitivity, operating mode (no flame level) | intermittent |
| Wiring polarity requirement | strictly observe polarity |
| Compatible burners | Riello, Baltur, Weishaupt, Lamborghini |
| Connection diagram | printed on housing |
| Installation recommendation | install in protective enclosure/cabinet |
| Remote reset support | yes |
| Advantage low voltage | ideal for low-voltage control circuits |
| Pre-purge time | 10 s |
| Net weight | 0.27 kg |
288.83 EUR
262.57EUR
in stock · 1
incl. 21% VAT · 217.00 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma BT2310 (article 18049400) is a microprocessor-based controller for automatic ignition control, flame monitoring, and safe operation of forced-draught gas, oil, and combination burners in intermittent mode. It operates on 12 V DC supply voltage and is suitable for single-stage or two-stage burners. The device features a pre-purge time of 10 seconds, a safety time of 10 seconds, and a flame loss reaction time of less than 1 second. It includes a built-in ignition transformer, two independent safety contacts, and supports ionisation, UV, or photodiode flame detectors. The controller has a non-volatile lockout with manual reset, remote reset capability, and a multicolour LED indicator. It weighs 0.27 kg and measures 90 x 85 x 65 mm, with an IP00 protection class (IP40 with base).
Further details
| Forced stop requirement | at least once every 24 hours |
|---|---|
| Initial startup requirement | ensure combustion chamber purged, electrode positioned |
| Interchangeability condition | only when supply voltage and timing parameters match |
| Maintenance | periodically check contacts, wiring, flame sensor |
| Reset Method | manual (reset button on housing) + remote reset |
| Reset procedure | find and eliminate cause, then press reset button |
| Voltage connection restriction | connection to 220 V or 24 V DC prohibited |
Choosing and fitting
Parts of this type are selected by matching the supply voltage, timing parameters (pre-purge and safety times), and flame detector type to the burner's requirements. The controller can be mounted in any position, but due to its IP00 rating, it should be installed in a protective enclosure or cabinet. Wiring must strictly observe polarity and the correct DC voltage level, as incorrect connection can damage the unit. The connection diagram is printed on the housing, and the base is not included and must be purchased separately.
Signs of failure
Items of this kind may fail by going into lockout due to abnormal conditions such as no flame, open ionisation circuit, or ignition failure. Symptoms include the burner not starting or shutting down unexpectedly, with the LED indicator showing fault codes. Common checks include verifying the flame sensor position and cleanliness, inspecting wiring integrity and contacts, and ensuring the supply voltage is correct. If a lockout occurs, the cause must be eliminated and the reset button pressed manually or remotely.
Fits equipment
Riello Baltur Weishaupt Lamborghini
All specifications
| Supply voltage | 12 V |
|---|---|
| Safety time | 10 s |
| Flame detector type | ionisation, UV, photodiode |
| Protection class (IP) | IP00 (with base - IP40) |
| Catalogue article numbers | 18049400, 246.124.152 |
| Installation position | any |
| Fuel | gas, oil, combination |
| Firing stages | single-stage / two-stage |
| Cycle type | intermittent |
| Flame loss reaction time | < 1 second |
| Safety feature | non-volatile lockout with manual reset |
| Service life under maximum load | 250000 |
| Dimensions | 90 x 85 x 65 mm |
| Operating temperatures | -20–70 °C |
| Storage temperature | -40–85 °C |
| Maximum humidity | 95 |
| Independent safety contacts | 2 contacts |
| Base present | no |
| Waiting time | verify on housing label |
| False flame check | yes |
| Automatic self-check | yes |
| Lockout alarm output | yes |
| Remote control | yes |
| LED indicators | multicolour LED |
| Built-in ignition transformer | yes |
| Sensitivity, operating mode (no flame level) | intermittent |
| Wiring polarity requirement | strictly observe polarity |
| Compatible burners | Riello, Baltur, Weishaupt, Lamborghini |
| Connection diagram | printed on housing |
| Installation recommendation | install in protective enclosure/cabinet |
| Remote reset support | yes |
| Advantage low voltage | ideal for low-voltage control circuits |
| Pre-purge time | 10 s |
| Net weight | 0.27 kg |
Part numbers
| SKU | 18049400 |
|---|---|
| Additional article | 246.124.152 |
| Model | BT2310 |
| Superseded number | 18049401 |
| Superseded number | 18049430 |