{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Brahma Burner control unit CE191.4 20658621

SKU 20658621 Model CE191.4 Brand Brahma

Photos

Key specifications

Supply voltage230 V
Safety time10 s
Flame detector typeionisation
Protection class (IP)IP40
Fuelgas
Air supplyforced draft
Service life under maximum load250000
Cycle typeintermittent
Flame detection methods supportedionisation
Flame loss reaction timeless than 1 second
Safety featureelectric reset (volatile lockout)
Flame monitoringionisation
Ambient temperature-20–60 °C
Pre-purge time30 s
Net weight0.275 kg
all specifications (15) ↓
170.10 EUR
154.64EUR
in stock · 2

incl. 21% VAT · 127.80 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Brahma CE191.4 burner control unit (SKU 20658621) is a control box for gas burners with forced draft, operating in intermittent mode. It manages ignition and flame monitoring via an ionisation electrode, with a safety time of 10 seconds and a pre-purge time of 30 seconds. The unit operates on 230 V supply voltage, has a protection class of IP40, and weighs 0.275 kg. It features an electric reset (volatile lockout) and reacts to flame loss in less than 1 second. The ambient temperature range is -20 to 60 °C, and the service life under maximum load is 250,000 cycles.

Further details

Applicationheating boilers, air heaters, infrared heaters, water heaters

Choosing and fitting

When selecting a replacement control box of this type, verify the supply voltage, safety time, and pre-purge time match the burner's requirements. The flame detector type (ionisation) must be compatible with the existing sensor. Ensure the unit's protection class and ambient temperature range suit the installation environment. Mounting may require a separate base, and the wiring diagram is typically printed on the housing. Compare the timing parameters on the old unit's label with the new one before installation.

Signs of failure

Typical failures of such control boxes include loss of flame signal, leading to a safety lockout indicated by a red LED. The burner may fail to ignite or shut down unexpectedly. Check the ionisation electrode for cleanliness and proper positioning, and verify the gas supply and air supply are adequate. If the unit locks out, it may require a power cycle to reset, depending on the reset mode.

All specifications

Supply voltage230 V
Safety time10 s
Flame detector typeionisation
Protection class (IP)IP40
Fuelgas
Air supplyforced draft
Service life under maximum load250000
Cycle typeintermittent
Flame detection methods supportedionisation
Flame loss reaction timeless than 1 second
Safety featureelectric reset (volatile lockout)
Flame monitoringionisation
Ambient temperature-20–60 °C
Pre-purge time30 s
Net weight0.275 kg

Part numbers

SKU20658621
Additional article246.124.033
ModelCE191.4
OEM equivalent20657621