{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Brahma Control box CM31U 37056010

SKU 37056010 Model CM31U Brand Brahma

Photos

Key specifications

Supply voltage230–230 V
Safety time10 s
Flame detector typeionisation
Protection class (IP)IP00
Body materialnon-flammable plastic
CertificationCE
Fuelgas
Firing stagesprogressive (modulating)
connection_typemicroflat-type connection base
Safety standardEN298:1993 and EN298:2003
Air supplywith or without fan
Service life under maximum load250000
Cycle typeintermittent
Flame detection methods supportedionisation
Flame loss reaction time<1 s
Safety featurenon-volatile lockout with manual reset
Installation positionany
Operating principlemicroprocessor controller
Flame monitoringionisation
Catalogue article numbers37056010, 246.124.067
Pre-purge time1.5 s
all specifications (21) ↓
175.69 EUR
159.72EUR
in stock · 3

incl. 21% VAT · 132.00 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Brahma Control box CM31U 37056010 is a microprocessor-based controller for atmospheric gas burners of progressive (modulating) type, operating with or without a fan. It features a non-volatile lockout with manual reset, ionisation flame monitoring with a reaction time of less than 1 second, and a safety time of 10 seconds. The device has a pre-purge time of 1.5 seconds, operates at 230 V AC, and is certified to EN298:1993 and EN298:2003 with CE marking. It is designed for intermittent operation and has a service life of 250,000 cycles under maximum load. The control box is housed in non-flammable plastic with IP00 protection and connects via a microflat-type base.

Choosing and fitting

Parts of this type are selected by matching the supply voltage, safety time, pre-purge time, and flame detection method to the burner's specifications. The connection type must be compatible with the existing base, and the control box must be installed in a protective enclosure with at least IP20 rating due to its IP00 protection. Ensure the mounting position is any, but the unit must be placed in a dry, ventilated area. Before ordering, verify the article number and model against the burner's documentation.

Signs of failure

When such controllers fail, the burner may lock out without restarting, indicated by a red LED. Common causes include a faulty flame sensor, incorrect wiring, or voltage surges. Check the ionisation electrode for contamination or wear, and verify the gas supply and electrical connections. If the unit locks out, press the manual reset button after resolving the issue.

Fits equipment

multiple atmospheric gas burners of progressive (modulating) type

All specifications

Supply voltage230–230 V
Safety time10 s
Flame detector typeionisation
Protection class (IP)IP00
Body materialnon-flammable plastic
CertificationCE
Fuelgas
Firing stagesprogressive (modulating)
connection_typemicroflat-type connection base
Safety standardEN298:1993 and EN298:2003
Air supplywith or without fan
Service life under maximum load250000
Cycle typeintermittent
Flame detection methods supportedionisation
Flame loss reaction time<1 s
Safety featurenon-volatile lockout with manual reset
Installation positionany
Operating principlemicroprocessor controller
Flame monitoringionisation
Catalogue article numbers37056010, 246.124.067
Pre-purge time1.5 s

Part numbers

SKU37056010
Additional article246.124.067
ModelCM31U