{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Brahma Microprocessor-based controller TGRD91 18047160

SKU 18047160 Model TGRD91 Brand Brahma

Photos

Key specifications

Safety time5 s
Flame detector typeionization
Fuelliquid fuel (diesel) and gas
Firing stagessingle-stage
Pre-purge time10 s
all specifications (5) ↓
170.90 EUR
155.36EUR
in stock · 11

incl. 21% VAT · 128.40 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Brahma TGRD91 is a microprocessor-based controller (burner manager) from the Kompact series, designed for full automation of ignition, flame monitoring, and safety of single-stage liquid fuel (diesel) air heaters and burners. It can also be used with gas atmospheric burners operating in intermittent mode. The device integrates a high-voltage ignition transformer, simplifying burner design. It features a pre-purge time of 10 seconds and a safety time of 5 seconds, with a non-volatile safety lockout that requires manual reset. Flame monitoring is via ionization, with a reaction time of less than 1 second in case of flame loss. This part number 18047160 is an original spare part for Master BV 47, BV 57, BV 77, BV 110, BV 170, and BV 290 series air heaters (since 2013).

Further details

Applicationheating systems for warehouses, production workshops, construction sites, and in process heating
Safety Featurenon-volatile safety lockout with manual reset

Choosing and fitting

Parts of this type are selected by matching the exact series and type designation, supply voltage, safety time, pre-purge time if applicable, and flame detection method (ionization, UV, or IR). The physical base or plug pattern must also match the existing socket. Burner controls are generally not interchangeable across series, even within one brand, because a mismatched safety time creates a safety hazard. Always verify the original part markings before ordering.

Signs of failure

Items of this kind typically fail by entering a lockout state due to no flame after the safety time, ionization circuit break, or ignition failure. The equipment stops fuel supply and requires manual reset after troubleshooting. Other failure modes include failure to start, intermittent operation, or no spark. Check the flame detector, ignition transformer, and wiring connections.

Fits equipment

Master BV 47, BV 57, BV 77, BV 110, BV 170, BV 290

All specifications

Safety time5 s
Flame detector typeionization
Fuelliquid fuel (diesel) and gas
Firing stagessingle-stage
Pre-purge time10 s

Part numbers

SKU18047160
Additional article246.124.134
ModelTGRD91
OEM equivalent4033.250