Brahma Microprocessor controller VM44G 37200761

SKU 37200761 Model VM44G Brand Brahma

Photos

no photo yet

Key specifications

Supply voltage220–240 V
Safety time2 s
Flame detector typeionization electrode
Protection class (IP)IP40
CertificationEN 298
Fuelgas
Firing stagessingle-stage or two-stage
Applicationforced draft gas burners
Safety standardEN 298
Service life under maximum load250000
Cycle typeintermittent
Flame detection methods supportedionisation
Safety featurenon-volatile lockout, manual reset
Actuator typeservo drive
Operating principlemicroprocessor controller
Flame monitoringionization
Catalogue article numbers37200761, 246.124.260
Pre-purge time30 s
Net weight0.4 kg
all specifications (19) ↓
300.15 EUR
272.86EUR
in stock · 2

incl. 21% VAT · 225.50 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Brahma VM44G microprocessor controller, SKU 37200761, is designed for automatic ignition control, flame monitoring, and safe operation of forced draft gas burners in intermittent mode. It operates on 220–240 V supply voltage, with a safety time of 2 seconds and a pre-purge time of 30 seconds. The controller uses an ionization electrode for flame detection and supports single-stage or two-stage burners. It features non-volatile lockout with manual reset, and is certified to EN 298. The net weight is 0.4 kg, protection class IP40, and it has a service life of 250,000 cycles under maximum load.

Further details

Application Typeautomatic ignition control, flame monitoring and safe operation

Choosing and fitting

Parts of this type are selected by matching the supply voltage, safety time, pre-purge time, flame detection method, and mounting base pattern to the original controller. Ensure compatibility with the burner's wiring base and confirm the flame detection method (ionisation, UV, or IR) before ordering. The control box governs the entire sequence, so any deviation in timing or logic can prevent proper operation or lockout. Always consult the burner manufacturer's documentation for the correct series and settings before substituting an equivalent control.

Signs of failure

When controllers of this kind fail, common symptoms include the burner failing to start, locking out without an obvious cause, or not responding to reset attempts. The equipment may show a lockout indication, and the flame signal may be lost or erratic. Check the flame detector, wiring connections, and supply voltage, and verify that the safety and pre-purge times are correctly set. If the controller locks out repeatedly, it may indicate a faulty flame detector, gas valve, or ignition transformer.

All specifications

Supply voltage220–240 V
Safety time2 s
Flame detector typeionization electrode
Protection class (IP)IP40
CertificationEN 298
Fuelgas
Firing stagessingle-stage or two-stage
Applicationforced draft gas burners
Safety standardEN 298
Service life under maximum load250000
Cycle typeintermittent
Flame detection methods supportedionisation
Safety featurenon-volatile lockout, manual reset
Actuator typeservo drive
Operating principlemicroprocessor controller
Flame monitoringionization
Catalogue article numbers37200761, 246.124.260
Pre-purge time30 s
Net weight0.4 kg

Part numbers

SKU37200761
Additional article246.124.260
ModelVM44G