Honeywell Gas control unit 0640520
SKU 0640520
Brand Honeywell
Photos
Key specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | 3 s |
| Protection class (IP) | IP44 |
| Waiting time | 9 s |
| Air proving switch | 6.0 s |
| Time delay term.6 / term.C | 10 s |
| Power consumption | 10 W |
| Amplifier sensitivity | 1 µA |
| Min. current from UV tube or ionisation probe | 5 µA |
| Weight incl. wiring base | 350 kg |
| Certification | EN 298, CE |
| Fuel | gas or oil |
| Firing stages | two-stage |
| Application | forced draught burners |
| Safety standard | EN 298 |
| Air supply | forced draft |
| Installation position | any |
| Pre-purge time | 24 s |
| Pre-ignition time | 3 s |
| Net weight | 0.35 kg |
1086.49 EUR
987.72EUR
in stock · 2
incl. 21% VAT · 816.30 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Honeywell Gas control unit 0640520 is a control box for two-stage forced draught burners, suitable for gas or oil fuel. It manages the burner sequence with a waiting time of 9 s, pre-purge time of 24 s, pre-ignition time of 3 s, and safety time of 3 s. The unit operates on a supply voltage of 220–240 V, consumes 10 W, and has an amplifier sensitivity of 1 µA with a minimum current from the UV tube or ionisation probe of 5 µA. It weighs 0.35 kg net, has protection class IP44, and is certified to EN 298 and CE. This control box fits the Honeywell MMG811.1 mod.33.
Further details
| AC frequency variations | result in proportional timing deviations |
|---|---|
| Classified acc. to EN 298 | BTLLXN |
| Flame Detector | ionisation probe, UV sensor, infrared flicker detector |
| Flame detector cable | max. 20 m cable length |
| Fuse rating | max. 10 A rapid, 6 A slow |
| Infrared flare detector | IRD 1020 |
| Insulation standard | IP 44 |
| Mounting attitude | any |
| Permissable ambient temp. | -20° C... +60°C |
| Reset delay | none |
Choosing and fitting
Parts of this type are selected by matching the supply voltage, safety time, and flame detector compatibility. The control box must be installed in any position, but the wiring base must be correctly connected. Before ordering, verify the burner's fuel type, stage count, and forced draught configuration. The unit's dimensions and mounting holes should be compared with the existing control box.
Signs of failure
Common failures include the burner not starting, repeated lockouts, or the flame signal not being detected. Check the flame detector cable for damage, ensure the air proving switch operates within 6 s, and verify the supply voltage is within the specified range. If the control box fails, the burner may shut down and require a manual reset.
Fits equipment
Honeywell MMG811.1 mod.33
All specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | 3 s |
| Protection class (IP) | IP44 |
| Waiting time | 9 s |
| Air proving switch | 6.0 s |
| Time delay term.6 / term.C | 10 s |
| Power consumption | 10 W |
| Amplifier sensitivity | 1 µA |
| Min. current from UV tube or ionisation probe | 5 µA |
| Weight incl. wiring base | 350 kg |
| Certification | EN 298, CE |
| Fuel | gas or oil |
| Firing stages | two-stage |
| Application | forced draught burners |
| Safety standard | EN 298 |
| Air supply | forced draft |
| Installation position | any |
| Pre-purge time | 24 s |
| Pre-ignition time | 3 s |
| Net weight | 0.35 kg |
Part numbers
| SKU | 0640520 |
|---|---|
| Additional article | 852.124.068 |