Honeywell Gas control unit DKG972-N mod. 10 0432010
SKU 0432010
Model DKG972-N mod. 10
Brand Honeywell
Photos
Key specifications
| Supply voltage | 230 V |
|---|---|
| Flame detector type | ionization |
| Protection class (IP) | IP40 |
| Consumption | 12 m3/h |
| Sensitivity, operating mode (no flame level) | 0.7 µA |
| Sensitivity to ambient light | 0.4 µA |
| Max. Ionization current | 26 µA |
| Weight | 175 g |
| Operating voltage | 230 V (-15...+10%) |
| Voltage tolerance | -15...+10% |
| Serial fuse | 10 a fast, 6 a slow |
| Min. required ionization current (flame level) | 1 mkA |
| EN 298 classification | atllxn |
| EN 298 compliance | EN 298:2003 |
| Fuel | gas |
| Firing stages | two-stage |
| Application type | atmospheric gas burners |
| Ice formation, water exposure and condensation | not allowed |
184.17 EUR
167.43EUR
in stock · 55
incl. 21% VAT · 138.37 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This Honeywell control box, model DKG972-N mod. 10 (SKU 0432010), is intended for controlling two-stage atmospheric gas burners with ionization flame detection. It operates at 230 V AC with a tolerance of -15% to +10%, and its consumption is 12 m³/h. The required minimum ionization current for flame detection is 1 µA; in no-flame operation the sensitivity is 0.7 µA, and sensitivity to ambient light is 0.4 µA. The maximum ionization current is 26 µA. The device has a protection class of IP40, weighs 175 g, and uses a serial fuse of 10 A fast or 6 A slow. It complies with EN 298:2003 and has EN 298 classification ATLLXN. Ice formation, water exposure, and condensation are not permitted.
Further details
| Classification EN298 | ATLLXN |
|---|---|
| Parasitic capacity | Probe – Ground less than 1000 pF |
| Probe isolation | Probe – Ground more than 50 M |
| Protection class | IP 40 |
| Serial fuse | 10 A fast, 6 A slow |
| Tested in accordance with the European standard | EN 298:2003, as well as all related regulations and directives |
All specifications
| Supply voltage | 230 V |
|---|---|
| Flame detector type | ionization |
| Protection class (IP) | IP40 |
| Consumption | 12 m3/h |
| Sensitivity, operating mode (no flame level) | 0.7 µA |
| Sensitivity to ambient light | 0.4 µA |
| Max. Ionization current | 26 µA |
| Weight | 175 g |
| Operating voltage | 230 V (-15...+10%) |
| Voltage tolerance | -15...+10% |
| Serial fuse | 10 a fast, 6 a slow |
| Min. required ionization current (flame level) | 1 mkA |
| EN 298 classification | atllxn |
| EN 298 compliance | EN 298:2003 |
| Fuel | gas |
| Firing stages | two-stage |
| Application type | atmospheric gas burners |
| Ice formation, water exposure and condensation | not allowed |
Part numbers
| SKU | 0432010 |
|---|---|
| Additional article | 534.412.084 |
| Model | DKG972-N mod. 10 |