Honeywell Gas control unit MMG810.1 mod.43 0642520
SKU 0642520
Model MMG810.1 mod.43
Brand Honeywell
Photos
Key specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | 3 s |
| Protection class (IP) | IP44 |
| Waiting time | 9 s |
| Air proving switch | 6.0 s |
| Time delay term.6 / term.C | 10 s |
| Power consumption | 10 W |
| Amplifier sensitivity | 1 µA |
| Min. current from UV tube or ionisation probe | 5 µA |
| Weight incl. wiring base | 350 kg |
| Pre-purge time | 40 s |
| Pre-ignition time | 3 s |
| Net weight | 0.35 kg |
1086.49 EUR
987.72EUR
in stock · 3
incl. 21% VAT · 816.30 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Honeywell MMG810.1 mod.43 is a gas control unit designed for forced draft and combined gas and oil burners of any nominal size. It operates with a supply voltage of 220–240 V and has a power consumption of 10 W. The unit features a waiting time of 9 s, a pre-purge time of 40 s, a pre-ignition time of 3 s, and a safety time of 3 s. It includes an air proving switch with a reaction time of 6.0 s and a time delay of 10 s between terminals 6 and C. The control unit has an amplifier sensitivity of 1 µA and requires a minimum current of 5 µA from a UV tube or ionisation probe. It weighs 0.35 kg net and has a protection class of IP44.
Further details
| AC frequency variations | result in proportional timing deviations |
|---|---|
| Classified acc. to EN 298 | BTLLXN |
| Flame Detector | ionisation probe, UV sensor, infrared flicker detector |
| Flame detector cable | max. 20 m cable length |
| Fuse rating | max. 10 A rapid, 6 A slow |
| Infrared flare detector | IRD 1020 |
| Insulation standard | IP 44 |
| Mounting attitude | any |
| Permissable ambient temp. | -20° C... +60°C |
| Reset delay | none |
Choosing and fitting
When selecting a replacement control box for a burner, ensure the supply voltage, timing sequences, and safety times match the burner's specifications. The control box must be compatible with the flame detector type (ionisation probe, UV sensor, or infrared flicker detector) and the wiring configuration. Check the mounting dimensions and protection class to fit the existing enclosure. Verify the power consumption and current requirements align with the burner's electrical system.
Signs of failure
Common failures in gas control units include failure to start, intermittent operation, or lockout due to flame detection issues. Symptoms may include the burner not igniting, shutting down after a short period, or displaying an error code. Check the flame detector, wiring connections, and supply voltage for faults. Also inspect the air proving switch and ensure proper airflow before the unit initiates the pre-purge cycle.
All specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | 3 s |
| Protection class (IP) | IP44 |
| Waiting time | 9 s |
| Air proving switch | 6.0 s |
| Time delay term.6 / term.C | 10 s |
| Power consumption | 10 W |
| Amplifier sensitivity | 1 µA |
| Min. current from UV tube or ionisation probe | 5 µA |
| Weight incl. wiring base | 350 kg |
| Pre-purge time | 40 s |
| Pre-ignition time | 3 s |
| Net weight | 0.35 kg |
Part numbers
| SKU | 0642520 |
|---|---|
| Additional article | 852.124.066 |
| Model | MMG810.1 mod.43 |