Honeywell Gas control unit MMG810.1 mod.43 0642520

SKU 0642520 Model MMG810.1 mod.43 Brand Honeywell

Photos

Key specifications

Supply voltage220–240 V
Safety time3 s
Protection class (IP)IP44
Waiting time9 s
Air proving switch6.0 s
Time delay term.6 / term.C10 s
Power consumption10 W
Amplifier sensitivity1 µA
Min. current from UV tube or ionisation probe5 µA
Weight incl. wiring base350 kg
Pre-purge time40 s
Pre-ignition time3 s
Net weight0.35 kg
all specifications (13) ↓
1086.49 EUR
987.72EUR
in stock · 3

incl. 21% VAT · 816.30 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Honeywell MMG810.1 mod.43 is a gas control unit designed for forced draft and combined gas and oil burners of any nominal size. It operates with a supply voltage of 220–240 V and has a power consumption of 10 W. The unit features a waiting time of 9 s, a pre-purge time of 40 s, a pre-ignition time of 3 s, and a safety time of 3 s. It includes an air proving switch with a reaction time of 6.0 s and a time delay of 10 s between terminals 6 and C. The control unit has an amplifier sensitivity of 1 µA and requires a minimum current of 5 µA from a UV tube or ionisation probe. It weighs 0.35 kg net and has a protection class of IP44.

Further details

AC frequency variationsresult in proportional timing deviations
Classified acc. to EN 298BTLLXN
Flame Detectorionisation probe, UV sensor, infrared flicker detector
Flame detector cablemax. 20 m cable length
Fuse ratingmax. 10 A rapid, 6 A slow
Infrared flare detectorIRD 1020
Insulation standardIP 44
Mounting attitudeany
Permissable ambient temp.-20° C... +60°C
Reset delaynone

Choosing and fitting

When selecting a replacement control box for a burner, ensure the supply voltage, timing sequences, and safety times match the burner's specifications. The control box must be compatible with the flame detector type (ionisation probe, UV sensor, or infrared flicker detector) and the wiring configuration. Check the mounting dimensions and protection class to fit the existing enclosure. Verify the power consumption and current requirements align with the burner's electrical system.

Signs of failure

Common failures in gas control units include failure to start, intermittent operation, or lockout due to flame detection issues. Symptoms may include the burner not igniting, shutting down after a short period, or displaying an error code. Check the flame detector, wiring connections, and supply voltage for faults. Also inspect the air proving switch and ensure proper airflow before the unit initiates the pre-purge cycle.

All specifications

Supply voltage220–240 V
Safety time3 s
Protection class (IP)IP44
Waiting time9 s
Air proving switch6.0 s
Time delay term.6 / term.C10 s
Power consumption10 W
Amplifier sensitivity1 µA
Min. current from UV tube or ionisation probe5 µA
Weight incl. wiring base350 kg
Pre-purge time40 s
Pre-ignition time3 s
Net weight0.35 kg

Part numbers

SKU0642520
Additional article852.124.066
ModelMMG810.1 mod.43