Kromschroder Burner control unit BCU460W3P2C0D0000K1E0-/LM400WF3O0E0- 88680312

SKU 88680312 Model BCU460W3P2C0D0000K1E0-/LM400WF3O0E0- Brand Kromschroder

Photos

no photo yet

Key specifications

Fuelgas
Application typeindustrial and commercial gas burners
Operation typeintermittent and continuous operation
CertificationEuropean standards, FM, EAC
Safety integrity levelSIL 3 (PL e)
Optical interfaceBCsoft optical interface
Electronic designfully electronic
Burner management systemcomplete
System pressure switch monitoringtemperature, fuel supply, airflow
Control functionsstart-up, control, protection
Automatic sequenceburner on/off sequence management
all specifications (11) ↓
3187.61 EUR
2897.83EUR
in stock · 1

incl. 21% VAT · 2394.90 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

This Kromschroder burner control unit (BCU460W3P2C0D0000K1E0-/LM400WF3O0E0-) is a complete burner management system for industrial and commercial gas burners. It is designed for intermittent and continuous operation and provides start-up, control, and protection functions. The unit manages the burner on/off sequence and monitors temperature, fuel supply, and airflow. Its fully electronic design includes a BCsoft optical interface for diagnostics and parameter setting. It is certified to European standards, FM, and EAC and is rated SIL 3 (PL e).

Further details

Displayprogram status, device parameters, and flame signal level
Frequent Cyclingideal for equipment with frequent start-stop cycles
Programmabilitythrough optical interface and BCsoft software

Choosing and fitting

Burner control units of this type are selected by exact series and type designation, supply voltage, required safety and pre-purge times, and flame detection method (ionisation, UV, or IR). The base or plug pattern must match the burner wiring harness. Controls from one series are generally not interchangeable with those from another, even from the same brand; a mismatched safety time creates a genuine safety risk. Before ordering, verify the existing unit’s part number and the burner’s specifications; the label on the control box gives the voltage and time settings.

Signs of failure

When a control unit of this kind fails to prove flame within the programmed safety time, it locks out. During operation, loss of flame causes the valve to close immediately, and the unit may attempt a restart or go to lockout. Repeated lockouts often trace to a faulty flame detector, bad pressure-switch inputs, or an incorrect safety-time setting; verify the fuel supply and airflow as part of troubleshooting.

All specifications

Fuelgas
Application typeindustrial and commercial gas burners
Operation typeintermittent and continuous operation
CertificationEuropean standards, FM, EAC
Safety integrity levelSIL 3 (PL e)
Optical interfaceBCsoft optical interface
Electronic designfully electronic
Burner management systemcomplete
System pressure switch monitoringtemperature, fuel supply, airflow
Control functionsstart-up, control, protection
Automatic sequenceburner on/off sequence management

Part numbers

SKU88680312
Additional article624.103.176
ModelBCU460W3P2C0D0000K1E0-/LM400WF3O0E0-