Key specifications
| Supply voltage | 230 V |
|---|---|
| Flame detector type | ionization or UV |
| Cycle type | intermittent or continuous |
| Fuel | gas |
| Duty cycle | 100 |
| Safety integrity level | SIL 3 / PL e |
| Type approvals | EC-type, FM, EAC |
| Flame detection methods supported | ionization or UV |
| Safety feature | Manual reset lockout |
| Ignition transformer voltage | 8 kV |
| Actuator type | LM400WF3O0E0 |
3477.90 EUR
3161.73EUR
in stock · 1
incl. 21% VAT · 2613.00 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This burner control unit is a gas-fired control box from Kromschroder. It operates on 230 V and supports a 100% duty cycle. Flame monitoring is performed by ionization or UV detection methods. It is designed for intermittent or continuous cycling and includes a manual reset lockout safety feature. The integrated actuator type is LM400WF3O0E0, and the unit carries an 8 kV ignition transformer. It meets SIL 3 / PL e safety integrity and holds EC-type, FM, and EAC approvals.
Further details
| All-in-one design | ignition unit, transformer, flame monitoring system, and air damper control module in one housing |
|---|---|
| Built-in display | shows current program status, device parameters, and flame signal level |
| Certifications | EC-type, FM, EAC, SIL 3 / PL E |
| Modular construction | includes ignition unit, transformer, flame monitoring system, and air damper control module in one housing |
Choosing and fitting
Parts of this type are selected by matching the exact series and type designation, supply voltage, safety and pre-purge times, flame detection method, and the physical base or plug pattern. The control also drives modulation when paired with an actuator or variable-speed fan, so actuator compatibility must be confirmed. A direct substitution should only be made if the original part number is verified against the burner's specification.
Signs of failure
If the flame is not proved within the programmed safety time, the control locks out and must be manually reset. The equipment will fail to start and require a reset. This is a safety function, not necessarily a failure of the control itself.
All specifications
| Supply voltage | 230 V |
|---|---|
| Flame detector type | ionization or UV |
| Cycle type | intermittent or continuous |
| Fuel | gas |
| Duty cycle | 100 |
| Safety integrity level | SIL 3 / PL e |
| Type approvals | EC-type, FM, EAC |
| Flame detection methods supported | ionization or UV |
| Safety feature | Manual reset lockout |
| Ignition transformer voltage | 8 kV |
| Actuator type | LM400WF3O0E0 |
Part numbers
| SKU | 88683322 |
|---|---|
| Additional article | 624.103.178 |
| Model | BCU460W3P2C0D1000K1E0-/LM400WF3O0E0- |