Kromschroder Combustion control unit BCU 560WC0F0U0D1K1-E 88670921
SKU 88670921
Model 560WC0F0U0D1K1-E
Brand Kromschroder
Photos
no photo yet
Key specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 1 s |
| Flame control mode | ionization |
| Operating time in manual mode | 5 minutes |
| Frequency | 50–60 Hz |
| Safety integrity level | SIL 3 (PL e) |
| Operating modes | continuous, intermittent, manual |
| Modular construction | replaceable power module |
| Flame check period | 2 s |
| Flame loss reaction time | instant |
| Optical interface | available |
| Net weight | 0.6 kg |
1427.50 EUR
1297.73EUR
in stock · 4
incl. 21% VAT · 1072.50 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This combustion control unit (model 560WC0F0U0D1K1-E) manages ignition and flame supervision in a gas burner. It operates from 230 V (50–60 Hz) and monitors the flame by ionization, reacting instantly to flame loss. The safety time is 1 s and the flame check period is 2 s. Operating modes include continuous, intermittent, and manual, with the manual mode limited to 5 minutes. It is rated SIL 3 (PL e), has a replaceable power module, and provides an optical interface for diagnostics. Net weight is 0.6 kg.
Further details
| Mounting feature | DIN rail in control cabinet; removable terminal blocks |
|---|---|
| Programmability | via optical interface and BCSoft software |
| Suitable systems | forced draft gas burners; direct ignition burners |
Choosing and fitting
Replacement control units of this kind are chosen by matching the exact series and type code, supply voltage, required safety and pre-purge times, flame detection method (ionization, UV, or IR), and base or plug pattern. Before ordering, compare these parameters with the original unit’s markings; a mismatched safety time or flame detector method creates a safety hazard. For installation, mount the unit on a DIN rail and connect fuel valves, ignition transformer, fan, pressure switches, and the flame detector as shown in the wiring diagram. After installation, verify that the selected mode and times are correctly set for the burner type.
All specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 1 s |
| Flame control mode | ionization |
| Operating time in manual mode | 5 minutes |
| Frequency | 50–60 Hz |
| Safety integrity level | SIL 3 (PL e) |
| Operating modes | continuous, intermittent, manual |
| Modular construction | replaceable power module |
| Flame check period | 2 s |
| Flame loss reaction time | instant |
| Optical interface | available |
| Net weight | 0.6 kg |
Part numbers
| SKU | 88670921 |
|---|---|
| Additional article | 624.124.068 |
| Model | 560WC0F0U0D1K1-E |