Kromschroder Burner control unit BCU460-3/1W3GBS3 88610022
SKU 88610022
Model BCU460-3/1W3GBS3
Brand Kromschroder
Photos
no photo yet
Key specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 3 s |
| Flame detector type | UV detector or ionization sensor |
| Protection class (IP) | IP54 |
| Cable for burner ground/PE wire | 4 mm2 |
| Maximum length of ionization/UV cable | 50 m |
| Weight | 5.1 g |
| Minimum burner pause time tBP | 0 s |
| Flame proving period 1, burner/pilot tFS1 | 0 s |
| Minimum time between two start-ups | 10 s |
| Fuel | gas |
| connection_type | hard wiring |
| Application | industrial burners |
| Cycle type | intermittent or continuous |
| Flame detection methods supported | ionization, UV |
| Safety feature | fault lock-out |
| Application type | automatic gas firing device control |
| Operating principle | fully electronic |
| Flame monitoring | yes |
| Ignition type | direct or pilot ignition |
| Ambient temperature | -20–60 °C |
| Net weight | 5.1 kg |
3391.65 EUR
3083.32EUR
in stock · 3
incl. 21% VAT · 2548.20 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder BCU460-3/1W3GBS3 (SKU 88610022) is a fully electronic burner control unit for automatic gas firing device control. It manages, ignites, and monitors gas burners for intermittent or continuous operation, suitable for industrial burners with direct or pilot ignition. The unit supports flame detection via ionization sensor or UV detector, with a safety time of 3 seconds and a minimum time between two start-ups of 10 seconds. It operates on 230 V supply voltage, has a protection class of IP54, and weighs 5.1 kg. The control unit features fault lock-out as a safety feature and is designed for hard wiring connection.
Further details
| 04 Switch-off threshold, burner/pilot burner | 1 micro A |
|---|---|
| Ambient temperature | -20 to +60°C, no condensation permitted |
| Enclosure | IP 54 pursuant to IEC 529 |
| Flame signal for ionization control | 1 – 28 μA, UV control: 1 – 35 μA |
| Inherent consumption | approx. 9 VA plus inherent consumption of the integrated ignition transformer |
| Mains voltage | 230 V AC, 50/60 Hz |
| Signal and control line | max. 2.5 mm2 |
Choosing and fitting
Parts of this type are selected by matching the control unit's supply voltage, flame detection method (ionization or UV), and safety time to the burner system's requirements. Installation involves hard wiring only, ensuring correct phase and neutral connection, and avoiding connection of voltage to valve or ignition outputs. The unit must be mounted near the burner, with cable lengths for ionization/UV not exceeding 50 m and burner ground/PE wire cross-section of 4 mm2. Ambient temperature range and protection class should be compatible with the installation environment.
Signs of failure
When such control units fail, common symptoms include burner lock-out due to fault detection, failure to ignite, or unexpected shutdown during operation. The equipment may display error codes or fault indications. Check for proper supply voltage, correct wiring, and integrity of flame detection components (ionization probe or UV sensor). Also inspect the fuse and ensure no moisture or condensation affects the unit, as it is rated for IP54 protection.
All specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 3 s |
| Flame detector type | UV detector or ionization sensor |
| Protection class (IP) | IP54 |
| Cable for burner ground/PE wire | 4 mm2 |
| Maximum length of ionization/UV cable | 50 m |
| Weight | 5.1 g |
| Minimum burner pause time tBP | 0 s |
| Flame proving period 1, burner/pilot tFS1 | 0 s |
| Minimum time between two start-ups | 10 s |
| Fuel | gas |
| connection_type | hard wiring |
| Application | industrial burners |
| Cycle type | intermittent or continuous |
| Flame detection methods supported | ionization, UV |
| Safety feature | fault lock-out |
| Application type | automatic gas firing device control |
| Operating principle | fully electronic |
| Flame monitoring | yes |
| Ignition type | direct or pilot ignition |
| Ambient temperature | -20–60 °C |
| Net weight | 5.1 kg |
Part numbers
| SKU | 88610022 |
|---|---|
| Additional article | 624.103.090 |
| Model | BCU460-3/1W3GBS3 |