Kromschroder Automatic burner control unit IFD258-3/1WI 84621615
SKU 84621615
Model IFD258-3/1WI
Brand Kromschroder
Photos
Key specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 3 s |
| Flame detector type | ionization or UV |
| Protection class (IP) | IP54 |
| Max. number of operating cycles | 250000 |
| Ambient temperature | -20–60 °C |
| Weight | 841 g |
| connection_type | hard wiring |
| Service life under maximum load | 250000 |
| Installation position | any |
| Cable gland | M16 |
| Net weight | 0.841 kg |
1513.41 EUR
1375.83EUR
in stock · 2
incl. 21% VAT · 1137.05 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder Automatic burner control unit IFD258-3/1WI (SKU 84621615) is a control box designed to ignite and supervise industrial gas burners without capacity limits. It operates with a supply voltage of 230 V and supports flame detection via ionization or UV sensors. The unit has a safety time of 3 seconds on start-up and can perform up to 250,000 operating cycles. It is rated IP54, weighs 841 g, and operates in ambient temperatures from -20 to 60 °C. Connection is via hard wiring with an M16 cable gland, and it can be installed in any position.
Further details
| Cable gland | M16 |
|---|---|
| Enclosure | IP 54 pursuant to IEC 529 |
| Installation position | any |
| Mains voltage | 230 V AC, 50/60 Hz |
| Relative humidity | no condensation permitted |
| Sensor current | > 2 µA |
| Sensor voltage | approx. 230 V AC |
Choosing and fitting
Parts of this type are selected by matching the supply voltage, flame detection method, and safety time to the burner system's requirements. The unit must be hard-wired, and the phase and neutral conductors must not be reversed. Ensure the burner is adequately grounded, and for single-electrode operation, only compatible ignition transformers (type TZI or TGI) are used. The installation position is flexible, but the cable gland size and protection class must suit the environment.
Signs of failure
When items of this kind fail, the burner may lock out or fail to ignite, often indicated by a fault signal. Common issues include incorrect wiring, insufficient grounding, or a faulty flame sensor. Check the flame signal intensity and the switch-off threshold adjustment, as well as the integrity of the ionization or UV sensor. If the unit repeatedly locks out, verify the safety time settings and the condition of the ignition transformer.
All specifications
| Supply voltage | 230 V |
|---|---|
| Safety time | 3 s |
| Flame detector type | ionization or UV |
| Protection class (IP) | IP54 |
| Max. number of operating cycles | 250000 |
| Ambient temperature | -20–60 °C |
| Weight | 841 g |
| connection_type | hard wiring |
| Service life under maximum load | 250000 |
| Installation position | any |
| Cable gland | M16 |
| Net weight | 0.841 kg |
Part numbers
| SKU | 84621615 |
|---|---|
| Additional article | 624.103.140 |
| Model | IFD258-3/1WI |