Kromschroder Burner control unit IFS110IM-10/1/1T 84367030
SKU 84367030
Model IFS110IM-10/1/1T
Brand Kromschroder
Photos
Key specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | 2–10 s |
| Flame detector type | ionization electrode or UV cell |
| Power consumption | 5 W |
| Ionisation electrode | 220 V |
| Ambient temperature | -20–60 °C |
| Weight | 750 g |
| Certification | EC tested and certified |
| Fuel | gas |
| Application | gas burners |
| Net weight | 0.75 kg |
2755.89 EUR
2505.35EUR
in stock · 1
incl. 21% VAT · 2070.54 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder IFS110IM-10/1/1T is a burner control unit for gas burners, designed to ignite and monitor the flame. It operates on a supply voltage of 220–240 V, consumes 5 W, and has a safety time of 2–10 s. The unit uses an ionization electrode or UV cell for flame detection, with an ionization electrode voltage of 220 V. It is certified to EC standards and weighs 750 g. The ambient temperature range is -20 to 60 °C.
Further details
| Cable gland | for Pg 9 |
|---|---|
| Contact load | max. 1 A per output |
| Fault indicator | lamp in the reset button and connection for external fault indicator |
| Fitting positon | arbitrary |
| Ignition time | approx. 1, 2, 3 or 7 s |
| Ionisation current | > 1 µA |
| Operating voltages | 220/240 V, 50/60 Hz |
| Protective grade | IP 40 acc. to DIN 40 050 |
| Reaction time | < 1s |
| Remote reset | yes |
| Safety time | 2, 3, 5 or 10 s |
| Total load | max. 2 A |
Choosing and fitting
When selecting a replacement control unit of this type, ensure the supply voltage, safety time, and flame detection method match the burner's requirements. The unit must be compatible with the burner's wiring and mounting configuration. Verify the ambient temperature range and weight constraints of the installation. Always compare the model specifications with the original part before ordering.
Signs of failure
Common failures include the unit not initiating ignition, frequent lockouts, or failure to detect flame. Symptoms may include the burner not starting, shutting down unexpectedly, or displaying a fault indication. Check the ionization electrode or UV cell for damage or contamination, and verify the supply voltage and wiring connections.
All specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | 2–10 s |
| Flame detector type | ionization electrode or UV cell |
| Power consumption | 5 W |
| Ionisation electrode | 220 V |
| Ambient temperature | -20–60 °C |
| Weight | 750 g |
| Certification | EC tested and certified |
| Fuel | gas |
| Application | gas burners |
| Net weight | 0.75 kg |
Part numbers
| SKU | 84367030 |
|---|---|
| Additional article | 624.103.060 |
| Model | IFS110IM-10/1/1T |