Kromschroder Burner control unit IFS110IM-3/1/1T 84367010

SKU 84367010 Model IFS110IM-3/1/1T Brand Kromschroder

Photos

Key specifications

Supply voltage220–240 V
Safety timeyes
Flame detector typeionization electrode or UV-cell
Power consumption5 W
Ionisation electrode220 V
Ambient temperature-20–60 °C
Weight750 g
Total load2 A
Cable glandfor PG 9 fitting
Installation positionarbitrary
CertificationEC tested and certified
Safety standardDIN 4788, VDE regulations
Housing typeimpact resistant plastic
Remote reset signalyes
Semiconductor automationyes
High switching frequencyyes
Behaviour in the event of flame failure during operationfault-lockout
Reset methodinternal or external push-button
Prepared cable entry holes7 holes
Flame detection methods supportedionization electrode or UV-cell
Flame monitoringcontinuous
Lockout on flame detection failureyes
Flame simulation checkyes
Suitable for ignition and ionization control with one electrodeyes
External fault indicationyes
Post-purgeyes
Flame extinguish check time10 s
Valve 2 activationat start
Lockout on flame simulationyes
Lockout on flame not extinguishyes
Net weight0.75 kg
all specifications (31) ↓
2755.89 EUR
2505.35EUR
in stock · 1

incl. 21% VAT · 2070.54 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder IFS110IM-3/1/1T is a burner control unit for gas burners in continuous operation. It manages ignition and flame monitoring using an ionization electrode or UV-cell, with continuous flame checking and a fault-lockout on flame failure or simulation. The unit operates at 220–240 V, consumes 5 W, and supports a total load of 2 A. It features a remote reset signal, external fault indication, and a flame extinguish check time of 10 seconds. The housing is impact-resistant plastic, and the device is EC tested and certified, conforming to DIN 4788 and VDE regulations.

Further details

Cable glandfor Pg 9
Construction typeplugin upper housing with controller and amplifying stage, plug socket with terminals, earthing strip and retaining screws
Contact loadmax. 1 A per output
Fault indicatorlamp in the reset button and connection for external fault indicator
Fitting positonarbitrary
Ignition timeapprox. 1, 2, 3 or 7 s
Ionisation current> 1 µA
Operating voltages220/240 V, 50/60 Hz
Protective gradeIP 40 acc. to DIN 40 050
Reaction time< 1s
Remote resetyes
Total loadmax. 2 A

Choosing and fitting

When selecting a replacement burner control unit, verify the supply voltage, power consumption, and total load ratings match the existing system. Ensure the flame detection method (ionization electrode or UV-cell) is compatible with the burner's sensor. Check the cable gland size (PG 9) and the number of cable entry holes (7) to match the wiring setup. The unit can be installed in any position, but ambient temperature must be within -20 to 60 °C.

Signs of failure

Typical failures of burner control units include lockout due to flame simulation or failure to extinguish, often indicated by a fault lamp or external signal. If the unit fails to detect a flame within the safety time, it will lock out and require a manual reset via the internal or external push-button. Check for loose connections, damaged electrodes, or incorrect wiring that may cause intermittent faults.

All specifications

Supply voltage220–240 V
Safety timeyes
Flame detector typeionization electrode or UV-cell
Power consumption5 W
Ionisation electrode220 V
Ambient temperature-20–60 °C
Weight750 g
Total load2 A
Cable glandfor PG 9 fitting
Installation positionarbitrary
CertificationEC tested and certified
Safety standardDIN 4788, VDE regulations
Housing typeimpact resistant plastic
Remote reset signalyes
Semiconductor automationyes
High switching frequencyyes
Behaviour in the event of flame failure during operationfault-lockout
Reset methodinternal or external push-button
Prepared cable entry holes7 holes
Flame detection methods supportedionization electrode or UV-cell
Flame monitoringcontinuous
Lockout on flame detection failureyes
Flame simulation checkyes
Suitable for ignition and ionization control with one electrodeyes
External fault indicationyes
Post-purgeyes
Flame extinguish check time10 s
Valve 2 activationat start
Lockout on flame simulationyes
Lockout on flame not extinguishyes
Net weight0.75 kg

Part numbers

SKU84367010
Additional article624.103.034
ModelIFS110IM-3/1/1T