Kromschroder Burner control unit IFS110IM-3/1/1T 84367010
SKU 84367010
Model IFS110IM-3/1/1T
Brand Kromschroder
Photos
Key specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | yes |
| Flame detector type | ionization electrode or UV-cell |
| Power consumption | 5 W |
| Ionisation electrode | 220 V |
| Ambient temperature | -20–60 °C |
| Weight | 750 g |
| Total load | 2 A |
| Cable gland | for PG 9 fitting |
| Installation position | arbitrary |
| Certification | EC tested and certified |
| Safety standard | DIN 4788, VDE regulations |
| Housing type | impact resistant plastic |
| Remote reset signal | yes |
| Semiconductor automation | yes |
| High switching frequency | yes |
| Behaviour in the event of flame failure during operation | fault-lockout |
| Reset method | internal or external push-button |
| Prepared cable entry holes | 7 holes |
| Flame detection methods supported | ionization electrode or UV-cell |
| Flame monitoring | continuous |
| Lockout on flame detection failure | yes |
| Flame simulation check | yes |
| Suitable for ignition and ionization control with one electrode | yes |
| External fault indication | yes |
| Post-purge | yes |
| Flame extinguish check time | 10 s |
| Valve 2 activation | at start |
| Lockout on flame simulation | yes |
| Lockout on flame not extinguish | yes |
| Net weight | 0.75 kg |
2755.89 EUR
2505.35EUR
in stock · 1
incl. 21% VAT · 2070.54 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder IFS110IM-3/1/1T is a burner control unit for gas burners in continuous operation. It manages ignition and flame monitoring using an ionization electrode or UV-cell, with continuous flame checking and a fault-lockout on flame failure or simulation. The unit operates at 220–240 V, consumes 5 W, and supports a total load of 2 A. It features a remote reset signal, external fault indication, and a flame extinguish check time of 10 seconds. The housing is impact-resistant plastic, and the device is EC tested and certified, conforming to DIN 4788 and VDE regulations.
Further details
| Cable gland | for Pg 9 |
|---|---|
| Construction type | plugin upper housing with controller and amplifying stage, plug socket with terminals, earthing strip and retaining screws |
| Contact load | max. 1 A per output |
| Fault indicator | lamp in the reset button and connection for external fault indicator |
| Fitting positon | arbitrary |
| Ignition time | approx. 1, 2, 3 or 7 s |
| Ionisation current | > 1 µA |
| Operating voltages | 220/240 V, 50/60 Hz |
| Protective grade | IP 40 acc. to DIN 40 050 |
| Reaction time | < 1s |
| Remote reset | yes |
| Total load | max. 2 A |
Choosing and fitting
When selecting a replacement burner control unit, verify the supply voltage, power consumption, and total load ratings match the existing system. Ensure the flame detection method (ionization electrode or UV-cell) is compatible with the burner's sensor. Check the cable gland size (PG 9) and the number of cable entry holes (7) to match the wiring setup. The unit can be installed in any position, but ambient temperature must be within -20 to 60 °C.
Signs of failure
Typical failures of burner control units include lockout due to flame simulation or failure to extinguish, often indicated by a fault lamp or external signal. If the unit fails to detect a flame within the safety time, it will lock out and require a manual reset via the internal or external push-button. Check for loose connections, damaged electrodes, or incorrect wiring that may cause intermittent faults.
All specifications
| Supply voltage | 220–240 V |
|---|---|
| Safety time | yes |
| Flame detector type | ionization electrode or UV-cell |
| Power consumption | 5 W |
| Ionisation electrode | 220 V |
| Ambient temperature | -20–60 °C |
| Weight | 750 g |
| Total load | 2 A |
| Cable gland | for PG 9 fitting |
| Installation position | arbitrary |
| Certification | EC tested and certified |
| Safety standard | DIN 4788, VDE regulations |
| Housing type | impact resistant plastic |
| Remote reset signal | yes |
| Semiconductor automation | yes |
| High switching frequency | yes |
| Behaviour in the event of flame failure during operation | fault-lockout |
| Reset method | internal or external push-button |
| Prepared cable entry holes | 7 holes |
| Flame detection methods supported | ionization electrode or UV-cell |
| Flame monitoring | continuous |
| Lockout on flame detection failure | yes |
| Flame simulation check | yes |
| Suitable for ignition and ionization control with one electrode | yes |
| External fault indication | yes |
| Post-purge | yes |
| Flame extinguish check time | 10 s |
| Valve 2 activation | at start |
| Lockout on flame simulation | yes |
| Lockout on flame not extinguish | yes |
| Net weight | 0.75 kg |
Part numbers
| SKU | 84367010 |
|---|---|
| Additional article | 624.103.034 |
| Model | IFS110IM-3/1/1T |