Siemens Burner control unit LME39.400C2
SKU LME39.400C2
Brand Siemens
Photos
Key specifications
| Body material | impact-proof, heat-resistant and flame-retarding plastic |
|---|---|
| Fuel | gas |
| Firing stages | two-stage |
| connection_type | plug-in |
| Air supply | forced draft |
272.46 EUR
247.69EUR
in stock · 1
incl. 21% VAT · 204.70 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Siemens LME39.400C2 is a microprocessor-based burner control unit for gas fan burners. It manages the complete ignition and safety sequence, including pre-purge, flame monitoring, gas valve control, and automatic fuel shut-off in case of faults. The unit is designed for two-stage burners and operates with forced draft air supply. It features a plug-in connection and is housed in impact-proof, heat-resistant, and flame-retarding plastic. The control supports ionization flame detection and is compatible with various flame sensors.
Further details
| Air Pressure Monitoring | reads signals from air and gas pressure switches |
|---|---|
| Application | domestic, commercial and industrial heating systems |
| Flame Detector | Ionization probe (ION) or flame detector QRA… with AGQ3…A27 |
Choosing and fitting
When selecting a replacement burner control of this type, verify the exact series designation and safety time, as mismatched timing profiles create a safety hazard. The physical plug-in base pattern must match the existing socket. Confirm the supply voltage and burner type (gas, forced draft, two-stage). The control is not interchangeable across different series even within the same brand. Ensure the flame detector type (ionization or UV with adapter) is compatible.
Signs of failure
Typical failures include lockout due to flame loss, no flame establishment at the end of safety time, or repeated ignition attempts. The equipment may shut down and require manual reset via the lockout button. Check for faulty or soiled fuel valves, flame detector issues, or poor burner adjustment. Also verify air and gas pressure switches and the safety loop.
Manufacturer documentation
All specifications
| Body material | impact-proof, heat-resistant and flame-retarding plastic |
|---|---|
| Fuel | gas |
| Firing stages | two-stage |
| connection_type | plug-in |
| Air supply | forced draft |
Part numbers
| SKU | LME39.400C2 |
|---|---|
| Additional article | 884.124.174 |