Siemens Combustion automaton LME41.051C2
SKU LME41.051C2
Brand Siemens
Photos
Key specifications
| Supply voltage | 230 V |
|---|---|
| Protection class (IP) | IP40 |
| Frequency range | 50–60 Hz |
| Fuse rating | 10 A |
| Cycle type | intermittent operation |
| Fuel | gas or gas/oil |
| Firing stages | 1- or 2-stage |
| Power consumption | 12 W |
| Interchangeability | not normally interchangeable across series |
142.79 EUR
129.81EUR
in stock · 1
incl. 21% VAT · 107.28 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Siemens LME41.051C2 is a combustion automaton for intermittent operation, designed for gas or gas/oil burners with 1- or 2-stage firing. It operates at a supply voltage of 230 V AC and a frequency range of 50–60 Hz. The unit consumes 12 W and has an IP40 protection class. A 10 A fuse is used to protect the control. It manages the ignition sequence, fuel admission, flame proving, and lockout functions.
Further details
| Driven components | ignition transformer, fuel valve, and fan |
|---|---|
| Monitored inputs | air pressure switch and flame detector |
| Operating sequence | pre-purge, ignition trial, fuel admission, flame proving, lockout on failure |
| Replacement guidance | verify type code, system voltage and timing requirements before ordering |
Choosing and fitting
Controls of this type are selected by the exact series and type designation, supply voltage, safety and pre-purge times, flame detection method (ionisation, UV, or IR), and the base or plug pattern. Always compare the type code on the existing control with the replacement data before ordering. These controls are not normally interchangeable across series, even within the same brand; a mismatched safety time creates a safety hazard, not merely an operational issue. The control may be base-mounted or plugged, and the wiring pattern must match the existing installation.
All specifications
| Supply voltage | 230 V |
|---|---|
| Protection class (IP) | IP40 |
| Frequency range | 50–60 Hz |
| Fuse rating | 10 A |
| Cycle type | intermittent operation |
| Fuel | gas or gas/oil |
| Firing stages | 1- or 2-stage |
| Power consumption | 12 W |
| Interchangeability | not normally interchangeable across series |
Part numbers
| SKU | LME41.051C2 |
|---|---|
| Additional article | 884.124.163 |