Siemens Burner automation controller LMO24.111C2

SKU LMO24.111C2 Brand Siemens

Photos

no photo yet

Key specifications

Supply voltage230 V
Safety time10 s
Flame detector typephotoresistive sensor
Fueloil
Firing stages2-stage
Cycle typeintermittent operation
Maximum oil burner throughput30 kg/h
Waiting time5 s
Pre-purge time16 s
Pre-ignition time15 s
all specifications (10) ↓
122.06 EUR
110.96EUR
in stock · 1

incl. 21% VAT · 91.70 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Siemens LMO24.111C2 is a burner automation control box for 2-stage oil burners with intermittent operation. It operates on 230 V AC and suits burners with a maximum throughput of 30 kg/h. Its safety time is 10 s, pre-purge time is 16 s, pre-ignition time is 15 s, and waiting time is 5 s. A photoresistive flame detector is used for flame monitoring.

Choosing and fitting

Controls of this type are selected by the exact series and type designation, supply voltage, required safety time and pre-purge time, and the flame detection method. The base or plug pattern must match the mounting arrangement, and controls of a given brand are normally not interchangeable across series. Before ordering, identify the part by its full type code and confirm it against the burner specification. When replacing, verify that the wiring diagram corresponds and that the flame detector type is compatible. Such controls are typically panel-mounted and wired to the burner terminal strip.

All specifications

Supply voltage230 V
Safety time10 s
Flame detector typephotoresistive sensor
Fueloil
Firing stages2-stage
Cycle typeintermittent operation
Maximum oil burner throughput30 kg/h
Waiting time5 s
Pre-purge time16 s
Pre-ignition time15 s

Part numbers

SKULMO24.111C2
Additional article884.124.115
Type designation4.04207.0
Type designation04042070