Brahma Phototransistor FT11/V 18209012
SKU 18209012
Model FT11/V
Brand Brahma
Photos
Key specifications
| Detection principle | infrared (IR) phototransistor |
|---|---|
| Catalogue article numbers | 246.901.024 (article); 18209012 (manufacturer code) |
| Cable length | 620 mm |
| Detection principle | infrared radiation |
| Device type | flame sensor / photodetector |
| Fuel | oil-fired or industrial burners |
| Output signal | electrical signal confirming combustion |
48.72 EUR
44.29EUR
in stock · 2
incl. 21% VAT · 36.60 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This infrared (IR) phototransistor is a flame sensor for oil-fired or industrial burners. It detects infrared radiation and produces an electrical signal that confirms combustion. The model is FT11/V, with a cable length of 620 mm. The manufacturer code is 18209012.
Further details
| Application | flame detector for oil-fired and industrial burners |
|---|---|
| Design Features | high thermal resistance and durable insulation |
| Line of sight | direct line of sight between detector and flame required |
| Maintenance Requirement | keep optical window clean; check sealing gasket; route cable away from hot surfaces |
| Purpose | flame detection and proof of combustion |
| Typical Failure Modes | contaminated window, weakened photocell, broken cable sheath |
Choosing and fitting
Replacement photodetectors of this kind are selected by matching spectral sensitivity (IR range), response time, cable length, connector type, and mounting sleeve design to the burner control. The connection is typically 2-wire or 3-wire. During installation on an oil burner, the sensor must be placed in a viewing port with direct line of sight to the flame. Ensure the optical window is clean, the sealing gasket is intact, and the cable is routed away from hot surfaces.
Signs of failure
Contamination of the optical window, a weakened photocell, or a damaged cable sheath are typical failure modes. Such faults may prevent the burner control from receiving a flame-confirmation signal, causing the burner to lock out or refuse to start. Check the window for soot, the cable for continuity and sheath damage, and the sealing gasket for integrity.
All specifications
| Detection principle | infrared (IR) phototransistor |
|---|---|
| Catalogue article numbers | 246.901.024 (article); 18209012 (manufacturer code) |
| Cable length | 620 mm |
| Detection principle | infrared radiation |
| Device type | flame sensor / photodetector |
| Fuel | oil-fired or industrial burners |
| Output signal | electrical signal confirming combustion |
Part numbers
| SKU | 18209012 |
|---|---|
| Additional article | 246.901.024 |
| Model | FT11/V |