Honeywell Flame sensor IRD1020.1 1653104
SKU 1653104
Model IRD1020.1
Brand Honeywell
Photos
Key specifications
| Detection principle | Infrared |
|---|---|
| Detection principle | Infrared |
| Catalogue article numbers | 1653104, 852.211.008 |
| Application type | Gas and oil burners |
| Sensing element | Photocell |
| Ambient temperature | -20–60 °C |
| Design features | Flicker detector, end-on viewing, blue |
| Frequency | 50–60 Hz |
| Supply voltage | 230 V |
246.94 EUR
224.49EUR
in stock · 1
incl. 21% VAT · 185.53 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Honeywell IRD1020.1 flame sensor (SKU 1653104, also listed as 852.211.008) is an infrared detector for gas and oil burners. It operates on 230 V with a frequency of 50–60 Hz and uses a photocell sensing element. The ambient temperature range is -20 to 60 °C. It is a flicker detector with end-on viewing and a blue housing. It is designed for use with Satronic control boxes TFI 812, DKG 97, DMG 97, and DLG 97.
Further details
| Application | Flame presence monitoring in burners and boilers |
|---|---|
| Compatible Control Type | Satronic burner control boxes (TFI 812, DKG 97, DMG 97, DLG 97) |
| Material | High-quality materials resistant to high temperatures and aggressive environments |
| Material quality | High-quality materials resistant to high temperatures and aggressive environments |
| Mounting | Requires special magnetic IRD flange M93 |
| Typical failure modes | contaminated optical window, aged photocell that produces a weakened signal, broken sheath that compromises the electrical connection |
Choosing and fitting
Parts of this type are chosen by matching the detection principle, spectral range, response time, cable length and connector type, as well as the mounting sleeve. The sensor must have a direct line of sight to the flame. Mounting configurations include end-on or side-on viewing, so the correct orientation must be selected for the burner's viewing port. The mounting flange must also be compatible; some detectors require a magnetic flange. Before ordering, ensure that the replacement has the same detection principle and that the viewing window is clean and correctly aligned with the flame.
Signs of failure
Typical failures of such sensors include a contaminated optical window, an aged photocell producing a weakened signal, or a broken sheath that compromises the electrical connection. When the sensor fails, the burner control will not receive a flame signal and will lock out, shutting off the fuel supply to prevent unsafe conditions. Check the viewing window for dirt or damage, measure the photocell output, and inspect the cable and sheath for wear. Also verify that the detector is correctly aligned and that the flame is within its field of view.
Manufacturer documentation
Interchangeable
Fits equipment
Satronic TFI 812, DKG 97, DMG 97, DLG 97
All specifications
| Detection principle | Infrared |
|---|---|
| Detection principle | Infrared |
| Catalogue article numbers | 1653104, 852.211.008 |
| Application type | Gas and oil burners |
| Sensing element | Photocell |
| Ambient temperature | -20–60 °C |
| Design features | Flicker detector, end-on viewing, blue |
| Frequency | 50–60 Hz |
| Supply voltage | 230 V |
Part numbers
| SKU | 1653104 |
|---|---|
| Additional article | 852.211.008 |
| Model | IRD1020.1 |