Kromschroder Flame sensor 84320303
SKU 84320303
Brand Kromschroder
Photos
no photo yet
Key specifications
| Detection principle | UV |
|---|---|
| Lens type | quartz glass |
| Sensor type | UV flame sensor |
| Housing material | aluminum |
| SKU (English) | 84320303, 624.208.026 |
| UV tube type | P578 |
| Cable gland type | M20 cable gland |
| Weight | 1000 g |
| Compatible burner controls | Kromschroder BCU and PFU |
| Frequency | 50–60 Hz |
| Connection thread | NPT 1/2 internal thread |
| Pollution degree | internal: 2, external: 4 |
| Cooling air connection | M20 cable gland |
| Cable gland thread size | M20 |
| Distance between UV flame detector and flame | 300–400 mm |
| Clamping range of the connection terminals | 0.5–1.5 mm2 |
| Weight | 1000 g |
| Ambient temperature | -20–80 °C |
| Storage temperature | -20–80 °C |
| Safety class | 1 |
| Cable length | 2000–100000 mm |
| Country of origin | Germany |
| material | aluminum |
| Cycle type | intermittent and continuous |
| Detection principle | UV detection |
| Sensing element | UV tube |
| Distance between UV sensor and flame | 300–400 mm |
| Catalogue article numbers | 624.208.026 |
| Supply voltage | 100–230 V |
1926.49 EUR
1751.35EUR
in stock · 1
incl. 21% VAT · 1447.40 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder Flame sensor 84320303 is a UV flame sensor designed for monitoring flames that emit UV radiation in industrial thermoprocessing setups. It operates with a supply voltage of 100–230 V AC at 50–60 Hz and features a quartz glass lens, aluminum housing, and a P578 UV tube. The sensor is compatible with Kromschroder BCU and PFU burner controls and has a connection thread of NPT 1/2 internal thread. It includes an M20 cable gland for cooling air connection and has a weight of 1000 g. The ambient and storage temperature range is -20 to 80 °C, and it is rated safety class 1 with pollution degree internal 2 and external 4.
Further details
| Certification | 2009/142/EC GAD, 2014/30/EU, 2014/35/EU, (EU) 2016/426 GAR |
|---|---|
| Compatible Control Type | Kromschroder burner control units BCU and PFU |
| Design Features | quartz glass heat guard lens, NPT 1/2 internal thread, cooling air connection M20 cable gland |
| Enclosure | IP 65 |
| Housing | aluminum |
| Min. DC signal | 1 μA |
| Operating Principle | detects UV radiation emitted by flame |
| Supply voltage | 100 to 230 V AC, 50/60 Hz (terminals L and N) |
| UV tube | P578, spectral range: 190 to 270 nm, max. sensitivity: 210 nm ± 10 nm |
Choosing and fitting
When selecting a replacement UV flame sensor of this type, ensure the supply voltage, frequency, and connection thread match the existing system. The sensor must be compatible with the burner control unit, and the cable length between the sensor and control unit should be within the specified range. The distance between the UV sensor and the flame must be adjusted to the recommended range for proper detection. The cable gland size and clamping range of connection terminals should also be verified for compatibility.
Signs of failure
Common failure modes for UV flame sensors include degradation of the UV tube, leading to reduced sensitivity or failure to detect the flame. This may cause the burner control to shut down or fail to start, often indicated by a fault code. Contamination of the quartz glass lens or improper alignment can also result in intermittent or no detection. Checking the sensor's output signal and cleaning the lens are typical diagnostic steps.
Fits equipment
Kromschroder BCU and PFU M20 cable gland
All specifications
| Detection principle | UV |
|---|---|
| Lens type | quartz glass |
| Sensor type | UV flame sensor |
| Housing material | aluminum |
| SKU (English) | 84320303, 624.208.026 |
| UV tube type | P578 |
| Cable gland type | M20 cable gland |
| Weight | 1000 g |
| Compatible burner controls | Kromschroder BCU and PFU |
| Frequency | 50–60 Hz |
| Connection thread | NPT 1/2 internal thread |
| Pollution degree | internal: 2, external: 4 |
| Cooling air connection | M20 cable gland |
| Cable gland thread size | M20 |
| Distance between UV flame detector and flame | 300–400 mm |
| Clamping range of the connection terminals | 0.5–1.5 mm2 |
| Weight | 1000 g |
| Ambient temperature | -20–80 °C |
| Storage temperature | -20–80 °C |
| Safety class | 1 |
| Cable length | 2000–100000 mm |
| Country of origin | Germany |
| material | aluminum |
| Cycle type | intermittent and continuous |
| Detection principle | UV detection |
| Sensing element | UV tube |
| Distance between UV sensor and flame | 300–400 mm |
| Catalogue article numbers | 624.208.026 |
| Supply voltage | 100–230 V |
Part numbers
| SKU | 84320303 |
|---|---|
| Additional article | 624.208.026 |