{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Flame sensor 84320303

SKU 84320303 Brand Kromschroder

Photos

no photo yet

Key specifications

Detection principleUV
Lens typequartz glass
Sensor typeUV flame sensor
Housing materialaluminum
SKU (English)84320303, 624.208.026
UV tube typeP578
Cable gland typeM20 cable gland
Weight1000 g
Compatible burner controlsKromschroder BCU and PFU
Frequency50–60 Hz
Connection threadNPT 1/2 internal thread
Pollution degreeinternal: 2, external: 4
Cooling air connectionM20 cable gland
Cable gland thread sizeM20
Distance between UV flame detector and flame300–400 mm
Clamping range of the connection terminals0.5–1.5 mm2
Weight1000 g
Ambient temperature-20–80 °C
Storage temperature-20–80 °C
Safety class1
Cable length2000–100000 mm
Country of originGermany
materialaluminum
Cycle typeintermittent and continuous
Detection principleUV detection
Sensing elementUV tube
Distance between UV sensor and flame300–400 mm
Catalogue article numbers624.208.026
Supply voltage100–230 V
all specifications (29) ↓
1926.49 EUR
1751.35EUR
in stock · 1

incl. 21% VAT · 1447.40 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder Flame sensor 84320303 is a UV flame sensor designed for monitoring flames that emit UV radiation in industrial thermoprocessing setups. It operates with a supply voltage of 100–230 V AC at 50–60 Hz and features a quartz glass lens, aluminum housing, and a P578 UV tube. The sensor is compatible with Kromschroder BCU and PFU burner controls and has a connection thread of NPT 1/2 internal thread. It includes an M20 cable gland for cooling air connection and has a weight of 1000 g. The ambient and storage temperature range is -20 to 80 °C, and it is rated safety class 1 with pollution degree internal 2 and external 4.

Further details

Certification2009/142/EC GAD, 2014/30/EU, 2014/35/EU, (EU) 2016/426 GAR
Compatible Control TypeKromschroder burner control units BCU and PFU
Design Featuresquartz glass heat guard lens, NPT 1/2 internal thread, cooling air connection M20 cable gland
EnclosureIP 65
Housingaluminum
Min. DC signal1 μA
Operating Principledetects UV radiation emitted by flame
Supply voltage100 to 230 V AC, 50/60 Hz (terminals L and N)
UV tubeP578, spectral range: 190 to 270 nm, max. sensitivity: 210 nm ± 10 nm

Choosing and fitting

When selecting a replacement UV flame sensor of this type, ensure the supply voltage, frequency, and connection thread match the existing system. The sensor must be compatible with the burner control unit, and the cable length between the sensor and control unit should be within the specified range. The distance between the UV sensor and the flame must be adjusted to the recommended range for proper detection. The cable gland size and clamping range of connection terminals should also be verified for compatibility.

Signs of failure

Common failure modes for UV flame sensors include degradation of the UV tube, leading to reduced sensitivity or failure to detect the flame. This may cause the burner control to shut down or fail to start, often indicated by a fault code. Contamination of the quartz glass lens or improper alignment can also result in intermittent or no detection. Checking the sensor's output signal and cleaning the lens are typical diagnostic steps.

Fits equipment

Kromschroder BCU and PFU M20 cable gland

All specifications

Detection principleUV
Lens typequartz glass
Sensor typeUV flame sensor
Housing materialaluminum
SKU (English)84320303, 624.208.026
UV tube typeP578
Cable gland typeM20 cable gland
Weight1000 g
Compatible burner controlsKromschroder BCU and PFU
Frequency50–60 Hz
Connection threadNPT 1/2 internal thread
Pollution degreeinternal: 2, external: 4
Cooling air connectionM20 cable gland
Cable gland thread sizeM20
Distance between UV flame detector and flame300–400 mm
Clamping range of the connection terminals0.5–1.5 mm2
Weight1000 g
Ambient temperature-20–80 °C
Storage temperature-20–80 °C
Safety class1
Cable length2000–100000 mm
Country of originGermany
materialaluminum
Cycle typeintermittent and continuous
Detection principleUV detection
Sensing elementUV tube
Distance between UV sensor and flame300–400 mm
Catalogue article numbers624.208.026
Supply voltage100–230 V

Part numbers

SKU84320303
Additional article624.208.026