Kromschroder Flame sensor UVC1L1G1A 84320300
SKU 84320300
Model UVC1L1G1A
Brand Kromschroder
Photos
no photo yet
Key specifications
| Detection principle | UV flame sensor |
|---|---|
| Distance between UV flame detector and flame | 300–400 mm |
| Clamping range of the connection terminals | 0.5–1.5 mm2 |
| Weight | 1000 g |
| Ambient temperature | -20–80 °C |
| Storage temperature | -20–80 °C |
| Safety class | 1 |
| material | aluminum housing |
| Cycle type | intermittent and continuous |
| Detection principle | UV radiation |
| Sensing element | UV tube |
| Electrical connection | terminals L and N |
| Distance between UV sensor and flame | 300–400 mm |
| Catalogue article numbers | 84320300, 624.208.024 |
| Designed lifetime | 10 years |
| Pollution degree | internal: 2, external: 4 |
| Cooling air connection | M20 cable gland |
| Cable gland thread size | M20 |
| Lens type | quartz glass |
| Sensor type | UV cell |
| Housing material | aluminum |
| SKU (English) | 84320300, 624.208.024 |
| UV tube type | P578 |
| Heat guard | quartz glass heat guard lens |
| Cable gland type | M20 cable gland |
| Weight | 1000 g |
| Compatible burner controls | Kromschroder BCU, PFU |
| Frequency | 50 Hz |
| Connection thread | RP 1/2 internal thread |
| Supply voltage | 100–230 V |
2219.58 EUR
2017.80EUR
in stock · 1
incl. 21% VAT · 1667.60 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder UVC1L1G1A flame sensor (SKU 84320300) is a UV-sensitive detector designed to monitor flames emitting UV radiation in industrial thermoprocessing systems. It operates with a supply voltage of 100–230 V AC at 50 Hz, using a P578 UV tube with a spectral range of 190–270 nm. The sensor is suitable for intermittent and continuous operation with Kromschroder BCU and PFU burner controls. It features an aluminum housing, quartz glass heat guard lens, RP 1/2 internal thread, and M20 cable gland. The distance between the UV flame detector and flame should be 300–400 mm, and the clamping range of connection terminals is 0.5–1.5 mm². The ambient and storage temperature range is -20 to 80 °C, with a safety class of 1 and designed lifetime of 10 years.
Further details
| Certification | 2009/142/EC GAD, 2014/30/EU, 2014/35/EU, (EU) 2016/426 GAR |
|---|---|
| Compatible Control Type | Kromschroder burner control units BCU, PFU |
| Design Features | quartz glass heat guard lens, RP 1/2 internal thread, cooling air connection M20 cable gland |
| Enclosure | IP 65 |
| Housing | aluminum |
| Min. DC signal | 1 μA |
| Pollution degree | internal environment: 2, eternal environment: 4 |
| Supply voltage | 100 to 230 V AC, 50/60 Hz (terminals L and N) |
| UV tube | P578, spectral range: 190 to 270 nm, max. sensitivity: 210 nm ± 10 nm |
Choosing and fitting
When selecting a replacement flame sensor of this type, ensure compatibility with the burner control unit (e.g., Kromschroder BCU or PFU) and verify the supply voltage and frequency. The sensor must be positioned at the correct distance from the flame (typically 300–400 mm) and connected via terminals L and N. Check the cable gland size (M20) and the internal thread (RP 1/2) to match the mounting. Also confirm the clamping range of connection terminals (0.5–1.5 mm²) and the ambient temperature limits.
Signs of failure
Common failure modes for UV flame sensors include degradation of the UV tube, leading to reduced sensitivity or failure to detect the flame. This may cause the burner control to lock out or fail to start. Check the sensor's lens for dirt or damage, and verify the electrical connections. If the sensor fails, the equipment may display an error code or shut down for safety.
Fits equipment
Kromschroder BCU, PFU M20 cable gland
All specifications
| Detection principle | UV flame sensor |
|---|---|
| Distance between UV flame detector and flame | 300–400 mm |
| Clamping range of the connection terminals | 0.5–1.5 mm2 |
| Weight | 1000 g |
| Ambient temperature | -20–80 °C |
| Storage temperature | -20–80 °C |
| Safety class | 1 |
| material | aluminum housing |
| Cycle type | intermittent and continuous |
| Detection principle | UV radiation |
| Sensing element | UV tube |
| Electrical connection | terminals L and N |
| Distance between UV sensor and flame | 300–400 mm |
| Catalogue article numbers | 84320300, 624.208.024 |
| Designed lifetime | 10 years |
| Pollution degree | internal: 2, external: 4 |
| Cooling air connection | M20 cable gland |
| Cable gland thread size | M20 |
| Lens type | quartz glass |
| Sensor type | UV cell |
| Housing material | aluminum |
| SKU (English) | 84320300, 624.208.024 |
| UV tube type | P578 |
| Heat guard | quartz glass heat guard lens |
| Cable gland type | M20 cable gland |
| Weight | 1000 g |
| Compatible burner controls | Kromschroder BCU, PFU |
| Frequency | 50 Hz |
| Connection thread | RP 1/2 internal thread |
| Supply voltage | 100–230 V |
Part numbers
| SKU | 84320300 |
|---|---|
| Additional article | 624.208.024 |
| Model | UVC1L1G1A |