Kromschroder Flame sensor UVS10D0G1 84315200
SKU 84315200
Model UVS10D0G1
Brand Kromschroder
Photos
Key specifications
| Detection principle | UV flame sensor |
|---|---|
| Distance between UV sensor and flame | 300–400 mm |
| Ambient temperature | -40–80 °C |
| Weight | 390 g |
| UV tube type | P578 |
| Service life | approx. 10.000 operating hours |
| Ingress protection | IP65 |
| Cable gland diameter | 7–13 mm |
| Housing material | aluminum |
| Heat guard | integrated heat guard |
| Catalogue article numbers | 84315200, 624.208.013 |
| Manufacturer part number | 84315200 |
| Application - Gas burners | flame control of gas burners |
| Electrical connection | connection terminals |
| SKU (English) | 84315200, 624.208.013 |
| Enclosure rating | IP65 |
| Weight | 390 g |
804.30 EUR
731.18EUR
in stock · 7
incl. 21% VAT · 604.28 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
Kromschroder UVS10D0G1 is a UV flame sensor designed for flame control of gas burners, used in conjunction with Elster Kromschroder automatic burner control units (IFS, IFD, PFS, PFD), flame detectors (IFW, PFF), or burner control units (BCU, PFU). It features an aluminum housing with an integrated heat guard and connection terminals. The sensor operates with a UV tube type P578, requiring a distance of 300–400 mm between the sensor and flame. It has an ambient temperature range of -40 to 80 °C, ingress protection IP65, and a weight of 390 g. The UV tube has a service life of approximately 10,000 operating hours.
Further details
| Cable gland | for cable diameters of 7 to 13 mm |
|---|---|
| Clamping range of the connection terminals | ≤ 2.5 mm² |
| Compatible Control Type | Elster Kromschroder automatic burner control units IFS, IFD, PFS, PFD, flame detectors IFW or PFF, burner control units BCU or PFU |
| Enclosure | IP 65 |
| Min. DC signal | 1 μA |
| Service life of the UV tube | approx. 10,000 operating hours |
| UV tube | P578, spectral range: 190–270 nm, max. sensitivity: 210 nm ± 10 nm |
Choosing and fitting
When selecting a replacement flame sensor of this type, ensure compatibility with the burner control unit and that the UV tube type matches the original specification. The distance between the sensor and flame must be within the recommended range, and the cable gland diameter should accommodate the existing cable (7–13 mm). Verify the ambient temperature range and ingress protection rating meet the installation environment. Mounting typically involves securing the sensor in a fixed position with proper alignment to the flame.
Signs of failure
Common failure modes for UV flame sensors include degradation of the UV tube, leading to reduced sensitivity or intermittent flame detection. This may cause the burner to shut down unexpectedly or fail to ignite. Check the sensor for contamination or damage to the UV tube, and verify the electrical connections are secure. If the sensor fails, the burner control unit may display a fault code indicating flame loss.
All specifications
| Detection principle | UV flame sensor |
|---|---|
| Distance between UV sensor and flame | 300–400 mm |
| Ambient temperature | -40–80 °C |
| Weight | 390 g |
| UV tube type | P578 |
| Service life | approx. 10.000 operating hours |
| Ingress protection | IP65 |
| Cable gland diameter | 7–13 mm |
| Housing material | aluminum |
| Heat guard | integrated heat guard |
| Catalogue article numbers | 84315200, 624.208.013 |
| Manufacturer part number | 84315200 |
| Application - Gas burners | flame control of gas burners |
| Electrical connection | connection terminals |
| SKU (English) | 84315200, 624.208.013 |
| Enclosure rating | IP65 |
| Weight | 390 g |
Part numbers
| SKU | 84315200 |
|---|---|
| Additional article | 624.208.013 |
| Model | UVS10D0G1 |