Kromschroder Flame sensor UVS10D0G1 84315200

SKU 84315200 Model UVS10D0G1 Brand Kromschroder

Photos

Key specifications

Detection principleUV flame sensor
Distance between UV sensor and flame300–400 mm
Ambient temperature-40–80 °C
Weight390 g
UV tube typeP578
Service lifeapprox. 10.000 operating hours
Ingress protectionIP65
Cable gland diameter7–13 mm
Housing materialaluminum
Heat guardintegrated heat guard
Catalogue article numbers84315200, 624.208.013
Manufacturer part number84315200
Application - Gas burnersflame control of gas burners
Electrical connectionconnection terminals
SKU (English)84315200, 624.208.013
Enclosure ratingIP65
Weight390 g
all specifications (17) ↓
804.30 EUR
731.18EUR
in stock · 7

incl. 21% VAT · 604.28 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

Kromschroder UVS10D0G1 is a UV flame sensor designed for flame control of gas burners, used in conjunction with Elster Kromschroder automatic burner control units (IFS, IFD, PFS, PFD), flame detectors (IFW, PFF), or burner control units (BCU, PFU). It features an aluminum housing with an integrated heat guard and connection terminals. The sensor operates with a UV tube type P578, requiring a distance of 300–400 mm between the sensor and flame. It has an ambient temperature range of -40 to 80 °C, ingress protection IP65, and a weight of 390 g. The UV tube has a service life of approximately 10,000 operating hours.

Further details

Cable glandfor cable diameters of 7 to 13 mm
Clamping range of the connection terminals≤ 2.5 mm²
Compatible Control TypeElster Kromschroder automatic burner control units IFS, IFD, PFS, PFD, flame detectors IFW or PFF, burner control units BCU or PFU
EnclosureIP 65
Min. DC signal1 μA
Service life of the UV tubeapprox. 10,000 operating hours
UV tubeP578, spectral range: 190–270 nm, max. sensitivity: 210 nm ± 10 nm

Choosing and fitting

When selecting a replacement flame sensor of this type, ensure compatibility with the burner control unit and that the UV tube type matches the original specification. The distance between the sensor and flame must be within the recommended range, and the cable gland diameter should accommodate the existing cable (7–13 mm). Verify the ambient temperature range and ingress protection rating meet the installation environment. Mounting typically involves securing the sensor in a fixed position with proper alignment to the flame.

Signs of failure

Common failure modes for UV flame sensors include degradation of the UV tube, leading to reduced sensitivity or intermittent flame detection. This may cause the burner to shut down unexpectedly or fail to ignite. Check the sensor for contamination or damage to the UV tube, and verify the electrical connections are secure. If the sensor fails, the burner control unit may display a fault code indicating flame loss.

All specifications

Detection principleUV flame sensor
Distance between UV sensor and flame300–400 mm
Ambient temperature-40–80 °C
Weight390 g
UV tube typeP578
Service lifeapprox. 10.000 operating hours
Ingress protectionIP65
Cable gland diameter7–13 mm
Housing materialaluminum
Heat guardintegrated heat guard
Catalogue article numbers84315200, 624.208.013
Manufacturer part number84315200
Application - Gas burnersflame control of gas burners
Electrical connectionconnection terminals
SKU (English)84315200, 624.208.013
Enclosure ratingIP65
Weight390 g

Part numbers

SKU84315200
Additional article624.208.013
ModelUVS10D0G1