Siemens Flame sensor RAR9

SKU RAR9 Brand Siemens

Photos

Key specifications

Catalogue article numbers884.211.002
Compatible control typeSiemens burner controls
Device typeflame sensor
Fueloil and gas
Performance featureshigh sensitivity, stable operation, durability
Response characteristicfast response to flame loss
all specifications (6) ↓
225.47 EUR
204.97EUR
in stock · 1

incl. 21% VAT · 169.40 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Siemens RAR9 flame sensor is a device for oil and gas burners, compatible with Siemens burner controls. It detects the presence or absence of a flame and sends a corresponding signal to the control. The sensor provides fast response to flame loss and features high sensitivity, stable operation, and durability.

Further details

Applicationboiler plants, diesel and gas burners, as well as industrial heat engineering equipment
Electrical Connectionconnected to the burner control or a dedicated flame amplifier
Maintenance Requirementclean viewing window and check cable integrity
Output Signalsignal to the burner control when flame is present or absent
Purposemonitor combustion process and send signal to burner control
Safety Functionemergency fuel shut-off in case of flame loss

Choosing and fitting

Flame sensors of this type are selected by the detection principle required by the burner control (ionisation, UV, or IR) and by spectral range to match the fuel—luminous oil or blue gas. The sensor must be positioned with a direct line of sight to the flame, typically using a sleeve or bracket. The cable length, connector type, and mounting arrangement must match the original part, and the original manufacturer code or catalogue number should be used to verify compatibility with the burner control.

Signs of failure

Common failure modes include a contaminated window or lens that reduces sensitivity, an aged sensing cell that gives a weakened signal, or a damaged cable that causes intermittent or no signal. When the sensor fails, the burner control may lock out after ignition because it does not detect flame within the safety time, preventing unburned fuel accumulation. Regular cleaning of the viewing window and inspecting the cable for cuts or strain can help maintain proper operation.

All specifications

Catalogue article numbers884.211.002
Compatible control typeSiemens burner controls
Device typeflame sensor
Fueloil and gas
Performance featureshigh sensitivity, stable operation, durability
Response characteristicfast response to flame loss

Part numbers

SKURAR9
Additional article884.211.002