{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Gas pressure regulator VGBF40R10-3 86047410

SKU 86047410 Model VGBF40R10-3 Brand Kromschroder

Photos

no photo yet

Key specifications

Nominal diameter (DN)40 mm
Connection threadRp 1½"
Max. inlet pressure1000 mbar
Setting range10–30 mbar
Safety standardEN 88, EN 334
Safety featurezero closure
Actuator typespring-loaded
Control featureshigh regulation accuracy
Ambient temperature-15–60 °C
Weight2900 g
Catalogue article numbers86047410, 624.658.052
Component typeGas pressure regulators
Inlet pressure compensationwith inlet pressure compensation
Compensation diaphragmcompensation diaphragm
Zero shut-offzero shut-off
Regulation accuracyhigh regulation accuracy
Qualitygerman quality honeywell kromschröder
Energy efficiencyenergy efficiency
SKU (English)86047410, 624.658.052
Gas type compatibilitynatural gas, liquefied gas, air
Factory setting20 mbar
connection_typeRp 1½" - internal thread
Applicationnatural gas, liquefied gas, air
Short nameKromschroeder VGBF40R10-3 (86047410) pressure regulator
Name (English)Kromschroeder VGBF40R10-3 (86047410) pressure regulator
Safety diaphragm ventingbuilt-in safety diaphragm
Venting arrangementno vent line required
CertificationCE
all specifications (28) ↓
1671.08 EUR
1519.16EUR
in stock · 1

incl. 21% VAT · 1255.50 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder VGBF40R10-3 gas pressure regulator, SKU 86047410, is a spring-loaded actuator with a nominal diameter of 40 mm and Rp 1½" internal thread connection. It handles a maximum inlet pressure of 1000 mbar and regulates outlet pressure within a range of 10–30 mbar, factory-set to 20 mbar. This model features inlet pressure compensation, a compensation diaphragm, zero shut-off, and a built-in safety diaphragm, eliminating the need for a vent line. It is certified to CE and complies with EN 88 and EN 334 standards, suitable for natural gas, liquefied gas, and air, operating in ambient temperatures from -15 to 60 °C and weighing 2900 g.

Further details

Advantagesgerman quality of honeywell kromschröder - maximum reliability and safety; high flow capacity and excellent pressure stability; built-in safety system (safety diaphragm); easy installation and minimal maintenance; long service life in intensive industrial
Application examplesindustrial and municipal boiler houses of medium capacity; burner devices and heat generators; gas supply systems for process equipment; industrial furnaces, drying chambers and production lines
Installation notesinstalled in the gas train downstream of the main shut-off valve and gas filter, and upstream of the gas valve
Maintenance Requirementeasy installation, adjustment and minimal maintenance
Purposemaintains a constant outlet pressure regardless of fluctuations in inlet pressure or flow demand
Replacement checkcheck the flow rate (n m³/h) at the operating pressure drop and ensure the connection size is correct
Selection criteriaselection of a gas pressure regulator is based on the required flow capacity at the expected inlet and outlet pressures, the gas type, and the connection size
Typical failurestorn diaphragm, drifting outlet pressure due to debris on the seat, or a blocked impulse line if used

Choosing and fitting

When selecting a gas pressure regulator of this type, ensure the connection size and thread type match the existing pipework, and verify that the maximum inlet pressure and outlet pressure range are compatible with the system's operating conditions. The regulator's set point is adjustable via spring preload, and the factory setting may need to be recalibrated to the required outlet pressure. Installation typically occurs downstream of the main shut-off valve and gas filter, and upstream of the gas valve, with the regulator oriented correctly to allow proper diaphragm function.

Signs of failure

Common failure modes for gas pressure regulators include a torn diaphragm, debris on the seat causing drifting outlet pressure, or a blocked impulse line if present. Symptoms may include unstable outlet pressure, inability to maintain set pressure, or gas leakage. Check the diaphragm for damage, clean the seat area, and inspect any impulse lines for blockages.

All specifications

Nominal diameter (DN)40 mm
Connection threadRp 1½"
Max. inlet pressure1000 mbar
Setting range10–30 mbar
Safety standardEN 88, EN 334
Safety featurezero closure
Actuator typespring-loaded
Control featureshigh regulation accuracy
Ambient temperature-15–60 °C
Weight2900 g
Catalogue article numbers86047410, 624.658.052
Component typeGas pressure regulators
Inlet pressure compensationwith inlet pressure compensation
Compensation diaphragmcompensation diaphragm
Zero shut-offzero shut-off
Regulation accuracyhigh regulation accuracy
Qualitygerman quality honeywell kromschröder
Energy efficiencyenergy efficiency
SKU (English)86047410, 624.658.052
Gas type compatibilitynatural gas, liquefied gas, air
Factory setting20 mbar
connection_typeRp 1½" - internal thread
Applicationnatural gas, liquefied gas, air
Short nameKromschroeder VGBF40R10-3 (86047410) pressure regulator
Name (English)Kromschroeder VGBF40R10-3 (86047410) pressure regulator
Safety diaphragm ventingbuilt-in safety diaphragm
Venting arrangementno vent line required
CertificationCE

Part numbers

SKU86047410
Additional article624.658.052
ModelVGBF40R10-3