Kromschroder Gas pressure regulator valve VAD350R/NW-100A 88000270
SKU 88000270
Model VAD350R/NW-100A
Brand Kromschroder
Photos
no photo yet
Key specifications
| Nominal diameter (DN) | 50 mm |
|---|---|
| Connection thread | Rp internal thread |
| Max. inlet pressure | 500 mbar |
| Safety feature | built-in protection |
| Operating principle | servo-operated |
| Control features | precise pressure regulation |
| connection_type | Rp threaded |
| Country of origin | Germany |
| Certification | EC, FM, CSA, UL |
| Output pressure range | 35–100 mbar |
| Closing time | ≤1 |
| Ingress protection | IP65 |
| Pressure test points | yes |
| Cable gland | M20 |
| Valve type | pressure regulator |
| Position indicator | yes |
| Pressure measuring points | yes |
| Fast response | yes |
| High control accuracy | yes |
| Stable combustion | yes |
| Gas savings | yes |
| Burner life extension | yes |
| No electrical coil | yes |
| Size series | 3 |
| Suitable for | atmospheric and forced-draft burners |
| Valve classification | A |
| Protection class (IP) | IP65 |
1915.71 EUR
1741.55EUR
in stock · 1
incl. 21% VAT · 1439.30 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder VAD350R/NW-100A is a servo-operated gas pressure regulator valve with a nominal diameter of 50 mm and Rp internal thread connection. It maintains outlet pressure within a range of 35–100 mbar, with a maximum inlet pressure of 500 mbar. The valve features a closing time of ≤1 second, IP65 ingress protection, and includes pressure test points, a position indicator, and a M20 cable gland. It is certified to EC, FM, CSA, and UL standards and is suitable for atmospheric and forced-draft burners. This regulator operates without an electrical coil, using a diaphragm and spring mechanism for precise pressure control.
Further details
| Application | industrial and municipal boiler houses, drying chambers, furnaces, heat treatment lines |
|---|---|
| Certification Standard | Class A (EN 88 and EN 161) |
| Gas Type | natural gas, LPG, biogas, clean air |
| Installation location | downstream of gas filter, upstream of main gas valves |
| Mechanical operation | purely mechanical via diaphragm and spring |
| Replacement check | confirm thread or flange size, spring range, zero-pressure type |
| Replacement note | if part of multiblock, ensure replacement matches original assembly |
| Solenoid configuration | two class A valves in series |
| Typical failures | diaphragm leakage, seized adjustment mechanism, drifting outlet pressure due to debris or wear |
Choosing and fitting
When selecting a replacement pressure regulator of this type, confirm the connection size and thread type (e.g., Rp threaded) to match the existing gas train. Verify the required outlet pressure range and maximum inlet pressure to ensure the spring range and valve rating are compatible. Check the valve classification and certifications needed for your application. Ensure the regulator is installed downstream of the filter and upstream of the main gas valves, with proper orientation and access for pressure test points.
Signs of failure
Common failures include diaphragm leakage, seized adjustment mechanisms, and drifting outlet pressure due to debris or wear. Symptoms may include unstable burner flame, inability to maintain set pressure, or gas leakage. Check the diaphragm for tears, inspect the adjustment mechanism for smooth operation, and clean any debris from the valve internals.
All specifications
| Nominal diameter (DN) | 50 mm |
|---|---|
| Connection thread | Rp internal thread |
| Max. inlet pressure | 500 mbar |
| Safety feature | built-in protection |
| Operating principle | servo-operated |
| Control features | precise pressure regulation |
| connection_type | Rp threaded |
| Country of origin | Germany |
| Certification | EC, FM, CSA, UL |
| Output pressure range | 35–100 mbar |
| Closing time | ≤1 |
| Ingress protection | IP65 |
| Pressure test points | yes |
| Cable gland | M20 |
| Valve type | pressure regulator |
| Position indicator | yes |
| Pressure measuring points | yes |
| Fast response | yes |
| High control accuracy | yes |
| Stable combustion | yes |
| Gas savings | yes |
| Burner life extension | yes |
| No electrical coil | yes |
| Size series | 3 |
| Suitable for | atmospheric and forced-draft burners |
| Valve classification | A |
| Protection class (IP) | IP65 |
Part numbers
| SKU | 88000270 |
|---|---|
| Additional article | 624.337.106 |
| Model | VAD350R/NW-100A |