Brahma Gas valve E6G*SR*1/2*CFD 13740750
SKU 13740750
Model E6G*SR*1/2*CFD
Brand Brahma
Photos
Key specifications
| Connection thread | Rp 1/2 |
|---|---|
| Supply voltage | 230 V |
| Closing time | 1 s |
| Installation position | vertical and horizontal |
| Body material | brass |
| Power supply type | direct current |
| Opening type | quick opening, silent |
| Valve class | a |
| Certification standard | EN161 |
| Directives | 90/396 and 93/68 |
| Installation standard | EN 60335-1 |
| Flow direction marking | arrow on the valve body |
| Nozzle diameter | 8 mm |
| Normally closed | normally closed type |
| Current type | direct and alternating current |
| Application purpose | domestic and industrial installations |
| Frequency | 60 Hz |
121.39 EUR
110.35EUR
in stock · 1
incl. 21% VAT · 91.20 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma Gas valve E6G*SR*1/2*CFD (SKU 13740750) is a normally closed type gas electromagnetic device designed for use in domestic and industrial installations. It operates on both direct and alternating current, with a supply voltage of 230 V and a frequency of 60 Hz. The valve features a quick opening, silent operation, and a closing time of 1 second. It has a brass body, a connection thread of Rp 1/2, and a nozzle diameter of 8 mm. The valve is certified to EN161 and complies with European directives 90/396 and 93/68, with installation per EN 60335-1.
Further details
| Connection Type | quick-release connection for din43650 - ip65 (gfd ip40) |
|---|---|
| Electrical safety | compliance with high standards and electrical safety requirements |
| Flow Adjustment | rotate clockwise to reduce gas flow, counterclockwise to increase gas flow |
| Flow Settings | the valve has the ability to adjust the flow rate |
| Flow rate adjustment | rotate clockwise to reduce gas flow, counterclockwise to increase gas flow |
| Foreign Object Prevention | make sure that no foreign objects get inside the valve |
| Hex Key Requirement | use an appropriately sized hex wrench |
| Pressure limit instruction | make sure that the inlet pressure ... does not exceed the value indicated on the valve itself |
| Protective Shell | avoid displacement of the protective shell |
Choosing and fitting
When selecting a gas valve of this type, ensure the connection thread size, supply voltage, and frequency match the system requirements. The valve can be installed vertically or horizontally, and the arrow on the body must align with the flow direction. The nozzle diameter (8 or 10 mm) must be appropriate for the application. Installation should follow national and European standards, including EN 60335-1 for electrical safety.
Signs of failure
Common failures in gas valves of this kind include sticking due to debris or coil burnout, leading to the valve failing to open or close properly. Symptoms may include no gas flow, continuous gas flow, or erratic burner operation. Check for foreign objects inside the valve, verify the coil resistance and supply voltage, and ensure the inlet pressure does not exceed the rated value.
All specifications
| Connection thread | Rp 1/2 |
|---|---|
| Supply voltage | 230 V |
| Closing time | 1 s |
| Installation position | vertical and horizontal |
| Body material | brass |
| Power supply type | direct current |
| Opening type | quick opening, silent |
| Valve class | a |
| Certification standard | EN161 |
| Directives | 90/396 and 93/68 |
| Installation standard | EN 60335-1 |
| Flow direction marking | arrow on the valve body |
| Nozzle diameter | 8 mm |
| Normally closed | normally closed type |
| Current type | direct and alternating current |
| Application purpose | domestic and industrial installations |
| Frequency | 60 Hz |
Part numbers
| SKU | 13740750 |
|---|---|
| Additional article | 246.322.004 |
| Model | E6G*SR*1/2*CFD |