Brahma Gas valve EG12*SR*GMO 13912001
SKU 13912001
Model EG12*SR*GMO
Brand Brahma
Photos
Key specifications
| Nominal diameter (DN) | 15 mm |
|---|---|
| Max. inlet pressure | 500 mbar |
| Supply voltage | 230 V |
| Closing time | 1 s |
| Opening time | 1 sec |
| Installation position | vertical and horizontal |
| Body | die-cast aluminum |
| Cable gland | pg9 |
| Opening type | fast, silent opening |
| Winding type | ac |
| connection_type | terminal block connection-ip40 |
| Certification standard | en161 |
| Directives | 90/396 and 93/68 |
| Valve classification | a |
| Gas group | 2 |
| Nozzle diameter | 15 mm |
| Filter element cell size | 1 mm |
| Rectifier | built-in rectifier bridge |
| Normally closed | normal closed type |
| Mesh filter at inlet | yes |
| Coil for DC supply | yes |
| Hydraulic shock absorber | yes |
| CE registration number | 63aq0626 |
| Frequency | 50–60 Hz |
| Power consumption | 20 W |
| Flow capacity | 7.5 m³/h |
| Net weight | 0.8 kg |
| Certification | CE |
182.88 EUR
166.25EUR
in stock · 3
incl. 21% VAT · 137.40 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma EG12*SR*GMO gas valve (SKU 13912001) is a normally closed solenoid valve designed for gas burners and boilers. It operates on 230 V AC (50–60 Hz) with a power consumption of 20 W, and features a built-in rectifier bridge for DC coil operation. The valve has a nominal diameter of 15 mm, a maximum inlet pressure of 500 mbar, and a flow capacity of 7.5 m³/h. It is certified to EN 161 (CE registration number 63AQ0626) and complies with directives 90/396 and 93/68. The die-cast aluminum body allows vertical or horizontal installation, and the valve includes a mesh filter at the inlet (1 mm cell size) and a hydraulic shock absorber for controlled opening.
Further details
| Adjustment Method | adjustment plugs to control the flow rate and initial flow during rapid opening, as well as pressure plugs at the inlet (all) or outlet |
|---|---|
| Adjustment plugs | flow rate and initial flow during rapid opening, pressure plugs at inlet/outlet |
| Application Purpose | designed for use in both the civil and industrial sectors |
| Flow Direction Marking | arrow on the gas control unit body |
| Foreign Object Prevention | make sure that no foreign objects have entered the body |
| Power Supply Flexibility | operate with both alternating and direct current |
| Pressure Limit Instruction | maximum fuel inlet pressure never exceeds the value indicated on the label |
| Silent Operation | equipped with a coil for direct current supply, ensuring silent operation |
| Variable Opening Modes | quick-opening function or slow opening, regulated by a special hydraulic shock absorber |
Choosing and fitting
When selecting a replacement gas valve of this type, verify the nominal diameter, maximum inlet pressure, supply voltage, and frequency match the system requirements. Ensure the valve's flow capacity is adequate for the burner's demand. Installation must align the arrow on the body with the direction of gas flow, and avoid twisting the shell during mounting—use a hex wrench on the valve body. The valve can be installed vertically or horizontally, and the electrical connection is via a terminal block with IP40 protection.
Signs of failure
Common failures in gas valves of this kind include coil burnout, which prevents the valve from opening, or debris clogging the inlet filter, causing reduced gas flow. A stuck valve may result in no gas supply or continuous flow, leading to burner ignition failure or unsafe operation. Check the coil resistance and supply voltage, inspect the filter for blockages, and verify the valve opens and closes within the specified times (1 second).
All specifications
| Nominal diameter (DN) | 15 mm |
|---|---|
| Max. inlet pressure | 500 mbar |
| Supply voltage | 230 V |
| Closing time | 1 s |
| Opening time | 1 sec |
| Installation position | vertical and horizontal |
| Body | die-cast aluminum |
| Cable gland | pg9 |
| Opening type | fast, silent opening |
| Winding type | ac |
| connection_type | terminal block connection-ip40 |
| Certification standard | en161 |
| Directives | 90/396 and 93/68 |
| Valve classification | a |
| Gas group | 2 |
| Nozzle diameter | 15 mm |
| Filter element cell size | 1 mm |
| Rectifier | built-in rectifier bridge |
| Normally closed | normal closed type |
| Mesh filter at inlet | yes |
| Coil for DC supply | yes |
| Hydraulic shock absorber | yes |
| CE registration number | 63aq0626 |
| Frequency | 50–60 Hz |
| Power consumption | 20 W |
| Flow capacity | 7.5 m³/h |
| Net weight | 0.8 kg |
| Certification | CE |
Part numbers
| SKU | 13912001 |
|---|---|
| Additional article | 246.322.013 |
| Model | EG12*SR*GMO |