Honeywell Gas valve VK4100C1000B
SKU VK4100C1000B
Brand Honeywell
Photos
Key specifications
| Max. inlet pressure | 60 mbar |
|---|---|
| Connection thread | flanged |
| Supply voltage | 24 V |
| Ambient temperature | -15–60 °C |
| Maximum working pressure | 45 bar |
| Voltage | 24 V |
| Purpose | gas flow control |
| Outlet Orientation | side outlet |
| Installation position | upright |
| Valve type | combined gas valve |
| Built-in valve | two main valves |
| Operating principle | positive feedback system |
| Control features | electric two-level regulator |
| Gas type | natural and liquefied gas |
| Electrical connection | connector or plug-in rectifier unit |
| Operating voltage | 24V |
| Housing type | standard housing |
| Diaphragm diameter | 2.8 mm |
| Pilot gas connection diameter | 4 mm |
| Inlet and outlet diameter | 18.6 mm |
| Back pressure (1st valve) | 50 mbar |
| Leakage requirements | EN126 |
| Nominal inlet gas pressure | 25 mbar |
| Pressure sensor pipe diameter | 0.5 inch |
| Operating position | upright |
| Maximum inlet pressure | 60 mbar |
| Maximum operating pressure | 45 mbar |
| Compression fitting | 4 mm |
| Max operating pressure | 45 mbar |
| Regulation of the mixture of gas and air in a ratio of 1 | 1 |
| Softlite pressure | 5 mbar |
| Softlite technology | smooth ignition |
| Ambient pressure | 1013 mbar |
| Built-in filter | fine-mesh filter |
| Throttle valve regulation | regulation via the throttle valve |
| Design features | positive feedback system |
| Input screen | on the input side |
| Two electrical devices | two electrical devices |
| Pressure drop | 3 mbar |
| Pressure relief valve | pressure relief valve |
| Filter cleaning | not intended for cleaning |
| Output pressure stability | stable output pressure |
| Softlite time | 1.5 sec. |
| Strainer cleaning | not intended for cleaning |
| Pressure servo controller | pressure servo controller |
| Smooth regulation with amplification | smooth regulation with amplification |
| Ignition regulator exception | s4565/s4585 series |
| Standard DBI ignition systems | plug-in rectifier unit |
| Output aperture diameter | 2.8 mm |
| Filter type | fine-mesh filter |
| Servo technology | servo |
| Flow capacity | 3.4 m³/h |
131.77 EUR
119.79EUR
in stock · 12
incl. 21% VAT · 99.00 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Honeywell VK4100C1000B is a combined gas valve designed for gas flow control in burner and boiler systems. It operates with natural and liquefied gas, featuring a positive feedback system and two main valves. The valve includes a built-in fine-mesh filter and supports smooth ignition via Softlite technology, with a Softlite time of 1.5 seconds. It has a maximum inlet pressure of 60 mbar, a maximum working pressure of 45 mbar, and a flow capacity of 3.4 m³/h at a pressure drop of 3 mbar. The valve is upright, has a side outlet, and connects via flanges with an inlet/outlet diameter of 18.6 mm.
Further details
| Back pressure | 1st valve: 50 mbar 2nd valve: 0 mbar |
|---|---|
| Capacity (by air) | 3.4 m3/h with a pressure drop of 3 mbar |
| Closing Variants | b + j, b + c, b + b |
| Control flow rate | 0.1 m3/h (min) of air at a pressure drop of 9 mbar |
| Gas connection | Inlet: diameter 18.6mm Outlet: side outlet diameter 18.6mm |
| Leakage requirements | According to EN126 |
| Mounting Feature | holes at the bottom for mounting |
| Optional Output Filter | additional output filter can be added |
| Pressure Measuring Fittings | silicone tubes with a diameter of 4 or 6 mm |
| Pressure Measuring Points | top for measuring inlet and outlet pressure |
| Pressure Test Points | top for measuring inlet and outlet pressure |
| Pressure valve | Top for measuring inlet and outlet pressure |
| Safety Feature | valve closes automatically when power is removed |
| Screen | On the input side |
| Softlite pressure | 5 mbar (-3.5/+0 after 1.5 sec.) adjustable |
Choosing and fitting
When selecting a replacement gas valve of this type, ensure the connection thread type (flanged), inlet/outlet diameters, and maximum working pressure match the system requirements. The valve must be installed upright, and the electrical connection (connector or plug-in rectifier unit) must be compatible with the existing ignition system. Verify the gas type (natural or liquefied) and the supply voltage (24 V) before installation. Also, check the ambient temperature range and ensure the valve's flow capacity meets the burner's demand.
Signs of failure
Common failures in combined gas valves include sticking or leaking valves due to debris or wear, leading to unstable gas flow or failure to close. Symptoms may include burner ignition failure, fluctuating flame, or gas odor. Check the fine-mesh filter for clogging (though not intended for cleaning) and inspect the pressure relief valve and servo controller for proper operation. If the valve fails to open or close, test the electrical connections and supply voltage.
All specifications
| Max. inlet pressure | 60 mbar |
|---|---|
| Connection thread | flanged |
| Supply voltage | 24 V |
| Ambient temperature | -15–60 °C |
| Maximum working pressure | 45 bar |
| Voltage | 24 V |
| Purpose | gas flow control |
| Outlet Orientation | side outlet |
| Installation position | upright |
| Valve type | combined gas valve |
| Built-in valve | two main valves |
| Operating principle | positive feedback system |
| Control features | electric two-level regulator |
| Gas type | natural and liquefied gas |
| Electrical connection | connector or plug-in rectifier unit |
| Operating voltage | 24V |
| Housing type | standard housing |
| Diaphragm diameter | 2.8 mm |
| Pilot gas connection diameter | 4 mm |
| Inlet and outlet diameter | 18.6 mm |
| Back pressure (1st valve) | 50 mbar |
| Leakage requirements | EN126 |
| Nominal inlet gas pressure | 25 mbar |
| Pressure sensor pipe diameter | 0.5 inch |
| Operating position | upright |
| Maximum inlet pressure | 60 mbar |
| Maximum operating pressure | 45 mbar |
| Compression fitting | 4 mm |
| Max operating pressure | 45 mbar |
| Regulation of the mixture of gas and air in a ratio of 1 | 1 |
| Softlite pressure | 5 mbar |
| Softlite technology | smooth ignition |
| Ambient pressure | 1013 mbar |
| Built-in filter | fine-mesh filter |
| Throttle valve regulation | regulation via the throttle valve |
| Design features | positive feedback system |
| Input screen | on the input side |
| Two electrical devices | two electrical devices |
| Pressure drop | 3 mbar |
| Pressure relief valve | pressure relief valve |
| Filter cleaning | not intended for cleaning |
| Output pressure stability | stable output pressure |
| Softlite time | 1.5 sec. |
| Strainer cleaning | not intended for cleaning |
| Pressure servo controller | pressure servo controller |
| Smooth regulation with amplification | smooth regulation with amplification |
| Ignition regulator exception | s4565/s4585 series |
| Standard DBI ignition systems | plug-in rectifier unit |
| Output aperture diameter | 2.8 mm |
| Filter type | fine-mesh filter |
| Servo technology | servo |
| Flow capacity | 3.4 m³/h |
Part numbers
| SKU | VK4100C1000B |
|---|---|
| Additional article | 534.331.919 |