Honeywell Gas valve VK4105C1066U
SKU VK4105C1066U
Brand Honeywell
Photos
Key specifications
| Max. inlet pressure | 60 mbar |
|---|---|
| Connection thread | 1/2" BSP.PL |
| Ambient temperature | -15–60 °C |
| Outlet Orientation | side gas outlet |
| Electrical connection | connector or plug-in rectifier unit |
| Operating voltage | 24V |
| Housing type | standard housing |
| Pilot gas connection diameter | 4 mm |
| Inlet and outlet diameter | 18.6 mm |
| Back pressure (1st valve) | 50 mbar |
| Leakage requirements | EN126 |
| Nominal inlet gas pressure | 25 mbar |
| Pressure sensor pipe diameter | 0.5 inch |
| Maximum inlet pressure | 60 mbar |
| Maximum operating pressure | 45 mbar |
| Softlite pressure | 7 mbar |
| Design features | positive feedback system |
| Input screen | on the input side |
| Pressure drop | 3 mbar |
| Output pressure stability | stable output pressure |
| Strainer cleaning | not intended for cleaning |
| Smooth regulation with amplification | smooth regulation with amplification |
| Flow capacity | 3.4 m³/h |
131.77 EUR
119.79EUR
in stock · 2
incl. 21% VAT · 99.00 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Honeywell VK4105C1066U is a gas valve designed for burner control and ignition systems, providing safe ignition, flame control, and gas flow regulation for pilot and/or main burners. It operates at 24V and features a standard housing with a side gas outlet. The valve has a maximum inlet pressure of 60 mbar, a nominal inlet pressure of 25 mbar, and a maximum operating pressure of 45 mbar. It includes a positive feedback system for stable output pressure and a softlite pressure of 7 mbar. The valve has a flow capacity of 3.4 m³/h with a pressure drop of 3 mbar, and its connection thread is 1/2" BSP.PL. It is suitable for use with heating gas, natural gas, and liquefied gas.
Further details
| Back pressure | 1st valve: 50 mbar 2nd valve: 0 mbar |
|---|---|
| Capacity (by air) | 3.4 m3/h with a pressure drop of 3 mbar |
| Gas connection | Inlet: 1/2" BSP.Pl Outlet hole: 1/2"BSP.Pl Side exhaust pipe |
| Leakage requirements | According to EN126 |
| Pressure Measuring Fittings | silicone tubes with diameter 4 or 6 mm |
| Pressure valve | Top for measuring inlet and outlet pressure |
| Screen | On the input side |
| Softlite pressure | 7 mbar (-3.5/+0 after 1.5 s) adjustable |
Choosing and fitting
Parts of this type are selected by matching the connection thread, operating voltage, and gas type. The valve must be installed with the correct orientation, typically vertical, and the inlet and outlet diameters (18.6 mm) must align with the piping. Ensure the ambient temperature range (-15 to 60 °C) is suitable for the installation environment. The electrical connection can be via a connector or plug-in rectifier unit, and the pilot gas connection diameter is 4 mm. Before ordering, verify the maximum inlet pressure and back pressure ratings against the system requirements.
Signs of failure
Common failures include the valve failing to open or close properly, leading to no gas flow or gas leakage. Symptoms may include burner ignition failure, unstable flame, or pressure fluctuations. Check for blockages in the inlet filter (not intended for cleaning) and ensure the electrical connections are secure. If the valve does not respond to control signals, test the coil and wiring for continuity.
All specifications
| Max. inlet pressure | 60 mbar |
|---|---|
| Connection thread | 1/2" BSP.PL |
| Ambient temperature | -15–60 °C |
| Outlet Orientation | side gas outlet |
| Electrical connection | connector or plug-in rectifier unit |
| Operating voltage | 24V |
| Housing type | standard housing |
| Pilot gas connection diameter | 4 mm |
| Inlet and outlet diameter | 18.6 mm |
| Back pressure (1st valve) | 50 mbar |
| Leakage requirements | EN126 |
| Nominal inlet gas pressure | 25 mbar |
| Pressure sensor pipe diameter | 0.5 inch |
| Maximum inlet pressure | 60 mbar |
| Maximum operating pressure | 45 mbar |
| Softlite pressure | 7 mbar |
| Design features | positive feedback system |
| Input screen | on the input side |
| Pressure drop | 3 mbar |
| Output pressure stability | stable output pressure |
| Strainer cleaning | not intended for cleaning |
| Smooth regulation with amplification | smooth regulation with amplification |
| Flow capacity | 3.4 m³/h |
Part numbers
| SKU | VK4105C1066U |
|---|---|
| Additional article | 534.322.001 |
| Type designation | VK4100 A 1002U |
| Type designation | VK4105C 1066B |