Key specifications
| Max. inlet pressure | 200 mbar |
|---|---|
| Connection thread | Rp 1 1/2 |
| Supply voltage | 220 V |
| Voltage | 220 V |
| Safety feature | Automatic closure on power loss |
| Electrical connection | PG11 cable gland |
| Operating voltage | 220 V |
| Ambient temperature | -20–60 °C |
| Maximum inlet pressure | 200 mbar |
| Maximum operating pressure | 200 mbar |
| Catalogue article numbers | 85208030, 624.322.073 |
| Ingress protection | IP54 |
| Cable gland | PG11 |
| Body material | AlSi |
| Seal material | Perbunan (NBR) |
| Filter material | Stainless steel |
| Built-in filter | Mesh filter at gas inlet |
| Flow adjustment | Adjustable |
| Threaded plug at inlet | Yes |
| Shut-off plate | Spring-loaded |
| High-load design | Yes |
| Certification | CE |
1217.41 EUR
1106.74EUR
in stock · 2
incl. 21% VAT · 914.66 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This gas solenoid valve from Kromschroder is used for safe control of gas burners, providing shut-off of gas flow. It operates at 220 V and has a connection thread of Rp 1 1/2, with maximum inlet and operating pressure of 200 mbar. The body is made of AlSi, with a Perbunan seal and stainless steel mesh filter at the inlet. It features automatic closure on power loss, a spring-loaded shut-off plate, adjustable flow, and a PG11 cable gland. The valve has IP54 ingress protection, an ambient temperature range of -20 to 60 °C, and is CE certified for high-load use.
Further details
| Application | Gas burners, boilers, furnaces, heat generators |
|---|---|
| Coil replaceability | Coil often available as separate spare part |
| Gas Type | Natural gas, liquefied gas, biogas (on request), air |
| Operating Position | Any position except upside down; coil orientation vertical upward to horizontal |
Choosing and fitting
Parts of this type are selected by matching the brand and series, connection size, coil voltage (typically 230 V or 24 V AC/DC), and the required function—single solenoid, double solenoid, slow-opening, or multiblock with filter and regulator. Before ordering, compare the connection thread and maximum operating pressure with the existing valve. Installation is possible in any position except upside down; the solenoid coil orientation may vary from vertical upward to horizontal. Ensure the valve is wired to the correct voltage and that the gas pressure switch confirms safe supply pressure before opening.
Signs of failure
Typical failures include coil burnout, which prevents the valve from opening; a leaking valve seat, causing gas to pass when the valve should be closed; drifting outlet pressure; or a seized servo regulator. A coil burnout is often indicated by no operation and a burnt smell; check coil resistance. A leaking seat may allow gas flow even without power—use leak detection. In such cases, the coil can often be replaced separately, reusing the valve body.
All specifications
| Max. inlet pressure | 200 mbar |
|---|---|
| Connection thread | Rp 1 1/2 |
| Supply voltage | 220 V |
| Voltage | 220 V |
| Safety feature | Automatic closure on power loss |
| Electrical connection | PG11 cable gland |
| Operating voltage | 220 V |
| Ambient temperature | -20–60 °C |
| Maximum inlet pressure | 200 mbar |
| Maximum operating pressure | 200 mbar |
| Catalogue article numbers | 85208030, 624.322.073 |
| Ingress protection | IP54 |
| Cable gland | PG11 |
| Body material | AlSi |
| Seal material | Perbunan (NBR) |
| Filter material | Stainless steel |
| Built-in filter | Mesh filter at gas inlet |
| Flow adjustment | Adjustable |
| Threaded plug at inlet | Yes |
| Shut-off plate | Spring-loaded |
| High-load design | Yes |
| Certification | CE |
Part numbers
| SKU | 85208030 |
|---|---|
| Additional article | 624.322.073 |
| Model | VG40/32R02NT31D |