Kromschroder Air/gas ratio control VAG125R/NWAK 88000349
SKU 88000349
Model VAG125R/NWAK
Brand Kromschroder
Photos
Key specifications
| Nominal diameter (DN) | 25 mm |
|---|---|
| Connection thread | Rp 1 |
| Supply voltage | 230 V |
| Ingress protection | IP65 |
| Valve classification | A |
| Regulator classification | A |
| Fast response | fast opening/closing |
| Frequency | 50–60 Hz |
1287.42 EUR
1170.38EUR
in stock · 1
incl. 21% VAT · 967.26 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder VAG125R/NWAK is a combined gas/air pressure regulator and solenoid valve for burner systems. It automatically meters gas flow in proportion to fan-delivered combustion air, keeping the gas/air ratio stable over the firing range. The valve has a nominal diameter of 25 mm with an Rp 1 internal thread, runs on 230 V AC at 50–60 Hz, and is rated IP65. Its valve and regulator are class A, and the mechanism opens and closes fast to minimize delays when operating conditions change.
Further details
| Control Features | automatically maintains the set gas/air pressure ratio |
|---|---|
| Valve Type | combined gas/air pressure regulator with solenoid valve |
Choosing and fitting
For air/gas ratio controls of this kind, replacement selection starts by comparing the pipe connection (threaded Rp 1/2” to 2” or flanged) and the coil voltage (230 V AC or 24 V AC/DC) with the existing system. The pneumatic impulse line—often marked 'nwak'—must be connected to the fan pressure tap; if the wrong tap is used or the line is blocked, the burner will not modulate correctly. Before fitting, also confirm the pressure switch setting against the manufacturer's instructions.
Signs of failure
Typical failures of these controls include a leaking servo diaphragm, a seized adjustment spindle, and a faulty solenoid coil. The burner may then show unstable gas/air ratio, fail to modulate, or run rich with elevated CO. Check the diaphragm for leaks, rotate the spindle through its range, and verify coil continuity. Also inspect the impulse line for blockages or leaks.
All specifications
| Nominal diameter (DN) | 25 mm |
|---|---|
| Connection thread | Rp 1 |
| Supply voltage | 230 V |
| Ingress protection | IP65 |
| Valve classification | A |
| Regulator classification | A |
| Fast response | fast opening/closing |
| Frequency | 50–60 Hz |
Part numbers
| SKU | 88000349 |
|---|---|
| Additional article | 624.322.138 |
| Model | VAG125R/NWAK |