{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Solenoid gas valve VAN120R/NQ 88012139

SKU 88012139 Model VAN120R/NQ Brand Kromschroder

Photos

Key specifications

Nominal diameter (DN)20 mm
Max. inlet pressure500 mbar
Connection threadRp 3/4
Ambient temperature-20–60 °C
Normally openyes
Gas typenatural gas, LPG, air, biogas
Valve typesolenoid relief valve
Position indicatorpilot lamp
Manufacturer code88012139, 624.337.003
Coil replaceabilityyes
Country of originGermany
CertificationCE
all specifications (12) ↓
1300.13 EUR
1181.94EUR
in stock · 1

incl. 21% VAT · 976.81 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder Solenoid gas valve VAN120R/NQ 88012139 is a normally open solenoid relief valve designed for automatic pressure relief and leak testing in gas systems. It has a nominal diameter of 20 mm with Rp 3/4 connection thread and a maximum inlet pressure of 500 mbar. Suitable for natural gas, LPG, air, and biogas, it operates in ambient temperatures from -20 to 60 °C. The valve is CE certified, made in Germany, and features a pilot lamp for position indication. Its coil is replaceable, and it is identified by manufacturer codes 88012139 and 624.337.003.

Further details

Advantagesfast pressure relief, high reliability, integrated indication, easy installation, compliance with standards
Application purposeindustrial and commercial gas burners, gas boilers and heat generators, gas supply systems downstream of pressure regulators, gas trains with leak testing
Installation locationbetween the gas filter and the burner
Purposerelief of excess pressure and leak testing
Replacement checkcheck connection size, coil voltage, single or double solenoid type, gas type compatibility, flow rate, outlet pressure setting
Typical failurescoil burnout, leaking seat, drifting outlet pressure, seized servo regulator

Choosing and fitting

When selecting a solenoid relief valve of this type, verify the connection thread size (e.g., Rp 3/4) and nominal diameter to match the existing piping. Ensure the maximum inlet pressure rating meets or exceeds the system's operating pressure. Confirm the valve's normally open or normally closed function aligns with the application's safety requirements. Check the coil voltage and replaceability, as coils may be ordered separately. Also, verify compatibility with the gas type and ambient temperature range.

Signs of failure

Common failures in solenoid relief valves include coil burnout, which prevents the valve from opening or closing properly, leading to pressure buildup or leakage. A leaking seat can cause continuous gas flow, resulting in pressure instability. If the valve fails to open, excess pressure may trigger other safety devices. Check the coil for continuity, inspect the seat for debris or wear, and verify the pilot lamp operation to diagnose issues.

All specifications

Nominal diameter (DN)20 mm
Max. inlet pressure500 mbar
Connection threadRp 3/4
Ambient temperature-20–60 °C
Normally openyes
Gas typenatural gas, LPG, air, biogas
Valve typesolenoid relief valve
Position indicatorpilot lamp
Manufacturer code88012139, 624.337.003
Coil replaceabilityyes
Country of originGermany
CertificationCE

Part numbers

SKU88012139
Additional article624.337.003
ModelVAN120R/NQ