Kromschroder Solenoid gas valve VAN120R/NQ 88012139
SKU 88012139
Model VAN120R/NQ
Brand Kromschroder
Photos
Key specifications
| Nominal diameter (DN) | 20 mm |
|---|---|
| Max. inlet pressure | 500 mbar |
| Connection thread | Rp 3/4 |
| Ambient temperature | -20–60 °C |
| Normally open | yes |
| Gas type | natural gas, LPG, air, biogas |
| Valve type | solenoid relief valve |
| Position indicator | pilot lamp |
| Manufacturer code | 88012139, 624.337.003 |
| Coil replaceability | yes |
| Country of origin | Germany |
| Certification | CE |
1300.13 EUR
1181.94EUR
in stock · 1
incl. 21% VAT · 976.81 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder Solenoid gas valve VAN120R/NQ 88012139 is a normally open solenoid relief valve designed for automatic pressure relief and leak testing in gas systems. It has a nominal diameter of 20 mm with Rp 3/4 connection thread and a maximum inlet pressure of 500 mbar. Suitable for natural gas, LPG, air, and biogas, it operates in ambient temperatures from -20 to 60 °C. The valve is CE certified, made in Germany, and features a pilot lamp for position indication. Its coil is replaceable, and it is identified by manufacturer codes 88012139 and 624.337.003.
Further details
| Advantages | fast pressure relief, high reliability, integrated indication, easy installation, compliance with standards |
|---|---|
| Application purpose | industrial and commercial gas burners, gas boilers and heat generators, gas supply systems downstream of pressure regulators, gas trains with leak testing |
| Installation location | between the gas filter and the burner |
| Purpose | relief of excess pressure and leak testing |
| Replacement check | check connection size, coil voltage, single or double solenoid type, gas type compatibility, flow rate, outlet pressure setting |
| Typical failures | coil burnout, leaking seat, drifting outlet pressure, seized servo regulator |
Choosing and fitting
When selecting a solenoid relief valve of this type, verify the connection thread size (e.g., Rp 3/4) and nominal diameter to match the existing piping. Ensure the maximum inlet pressure rating meets or exceeds the system's operating pressure. Confirm the valve's normally open or normally closed function aligns with the application's safety requirements. Check the coil voltage and replaceability, as coils may be ordered separately. Also, verify compatibility with the gas type and ambient temperature range.
Signs of failure
Common failures in solenoid relief valves include coil burnout, which prevents the valve from opening or closing properly, leading to pressure buildup or leakage. A leaking seat can cause continuous gas flow, resulting in pressure instability. If the valve fails to open, excess pressure may trigger other safety devices. Check the coil for continuity, inspect the seat for debris or wear, and verify the pilot lamp operation to diagnose issues.
All specifications
| Nominal diameter (DN) | 20 mm |
|---|---|
| Max. inlet pressure | 500 mbar |
| Connection thread | Rp 3/4 |
| Ambient temperature | -20–60 °C |
| Normally open | yes |
| Gas type | natural gas, LPG, air, biogas |
| Valve type | solenoid relief valve |
| Position indicator | pilot lamp |
| Manufacturer code | 88012139, 624.337.003 |
| Coil replaceability | yes |
| Country of origin | Germany |
| Certification | CE |
Part numbers
| SKU | 88012139 |
|---|---|
| Additional article | 624.337.003 |
| Model | VAN120R/NQ |