Kromschroder Gas solenoid valve VG10R01T6 85233010
SKU 85233010
Model VG10R01T6
Brand Kromschroder
Photos
Key specifications
| Nominal diameter (DN) | 10 mm |
|---|---|
| Max. inlet pressure | 100 mbar |
| Connection thread | Rp |
| Supply voltage | 230 V |
| Valve type | solenoid gas valve |
| Electrical connection | 3-pin standard connector |
| Opening time | fast |
| Safety feature | automatic gas shut-off when de-energized |
| Normal state | normally closed |
| Coil replaceability | replaceable |
| Frequency | 60 Hz |
| Country of origin | Germany |
| Certification | EN 161 |
420.84 EUR
382.58EUR
in stock · 2
incl. 21% VAT · 316.18 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder VG10R01T6 is a normally closed solenoid gas valve with a nominal diameter of 10 mm and Rp thread connection. It operates at a maximum inlet pressure of 100 mbar and requires a 230 V, 60 Hz supply. The valve features fast opening and automatic gas shut-off when de-energized, ensuring safety. It is certified to EN 161 and comes with a replaceable coil and a 3-pin standard connector. This valve is suitable for use in gas trains, burners, and boilers.
Further details
| Application | gas trains, burners, boilers, engineering installations |
|---|---|
| Gas type | natural gas, town gas, LPG, air |
| Replacement note | verify connection size, coil voltage, function |
Choosing and fitting
When selecting a replacement solenoid gas valve of this kind, verify the connection size (nominal diameter and thread type), coil voltage, and frequency match the original. Ensure the valve's maximum inlet pressure rating is adequate for the system. The valve should be installed with the flow direction as indicated, and the electrical connection must be compatible with the existing wiring. Check that the valve's function (e.g., normally closed, fast opening) aligns with the application requirements.
Signs of failure
Common failure modes for solenoid gas valves include coil burnout, which may cause the valve to fail open or closed, and leaking seats, leading to gas passage when the valve is off. Debris or corrosion can cause the valve to stick, preventing proper opening or closing. Symptoms on equipment include failure to ignite, burner lockout, or gas odor. Check the coil for continuity and resistance, inspect the valve seat for debris, and verify the valve opens and closes with applied voltage.
All specifications
| Nominal diameter (DN) | 10 mm |
|---|---|
| Max. inlet pressure | 100 mbar |
| Connection thread | Rp |
| Supply voltage | 230 V |
| Valve type | solenoid gas valve |
| Electrical connection | 3-pin standard connector |
| Opening time | fast |
| Safety feature | automatic gas shut-off when de-energized |
| Normal state | normally closed |
| Coil replaceability | replaceable |
| Frequency | 60 Hz |
| Country of origin | Germany |
| Certification | EN 161 |
Part numbers
| SKU | 85233010 |
|---|---|
| Additional article | 624.331.059 |
| Model | VG10R01T6 |