Kromschroder Gas solenoid valve VG15/12R18NT31 85265010
SKU 85265010
Model VG15/12R18NT31
Brand Kromschroder
Photos
Key specifications
| Max. inlet pressure | 1800 mbar |
|---|---|
| Connection thread | Rp 1/2" |
| Ambient temperature | -20–60 °C |
| Ingress protection | IP54 |
| Opening time | 0.5 sec |
| Closing time | less than 1 |
| Body material | aluminum alloy |
| Seal material | perbunan |
| Installation options | vertical, horizontal or angled |
| Coil voltage type | black solenoid coil |
1027.80 EUR
934.36EUR
in stock · 2
incl. 21% VAT · 772.20 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Kromschroder VG15/12R18NT31 is a normally closed gas solenoid valve with SKU 85265010, designed for automatic gas shut-off in burner and boiler systems. It features a Rp 1/2" internal thread, a maximum inlet pressure of 1800 mbar, and operates within an ambient temperature range of -20 to 60 °C. The valve opens in 0.5 seconds and closes in less than 1 second, with an IP54 ingress protection rating. Its body is made of aluminum alloy, and the seal is perbunan. It can be installed vertically, horizontally, or at an angle, and is equipped with a black solenoid coil.
Further details
| Application | gas supply line between the main shut-off cock and the burner |
|---|---|
| Compatibility check | must match original connection size and electrical supply; coil voltage identical to burner control output; compatible with gas type and max working pressure |
| Function | open and close the gas flow on command from the burner control |
| Gas type | natural gas, town gas and liquefied petroleum gas (lpg) |
| Premix burner compatibility | pneumatic gas/air ratio regulator links the valve to the fan |
| Pressure switch requirement | gas pressure switch confirms supply pressure within safe range |
| Replacement note | coil often available separately from valve body |
| Typical failures | coil burnout, leaking valve seat, drifting outlet pressure, seized servo regulator |
Choosing and fitting
When selecting a replacement gas solenoid valve of this type, ensure the connection thread size, coil voltage, and maximum working pressure match the original. The valve body can be mounted in vertical, horizontal, or angled orientations, but the installation must prevent condensation. Verify the gas type compatibility (e.g., natural gas, LPG) and that the valve's pressure rating meets or exceeds the system's maximum pressure. Always compare the connection size and electrical supply before ordering.
Signs of failure
Common failure modes for this kind of valve include coil burnout, leaking valve seat, drifting outlet pressure, and a seized servo regulator. Symptoms may include the burner failing to ignite, gas flow continuing when it should stop, or inconsistent flame behavior. Check the coil for continuity, inspect the valve seat for debris or wear, and verify the outlet pressure against the setpoint.
All specifications
| Max. inlet pressure | 1800 mbar |
|---|---|
| Connection thread | Rp 1/2" |
| Ambient temperature | -20–60 °C |
| Ingress protection | IP54 |
| Opening time | 0.5 sec |
| Closing time | less than 1 |
| Body material | aluminum alloy |
| Seal material | perbunan |
| Installation options | vertical, horizontal or angled |
| Coil voltage type | black solenoid coil |
Part numbers
| SKU | 85265010 |
|---|---|
| Additional article | 624.331.038 |
| Model | VG15/12R18NT31 |