Brahma Ignition transformer 15910752
SKU 15910752
Brand Brahma
Photos
Key specifications
| Supply voltage | 50–60 V |
|---|---|
| Secondary voltage | 12–12 kV |
| Poles / outlets | 2 |
| Construction type | high-frequency electronic generator |
| Protection | IP00 |
| Compatible controllers | Brahma controllers |
| Peak current (mA) | 55 mA |
| Output voltage frequency | 12 kHz |
| Protection class (IP) | IP00 |
| Recommended spark distance | 3–5 mm |
| Maximum length of ignition cable with integrated electronic ignition | 1.5 m |
| Standard power cable length | 560 mm |
| Weight (approx) | about 420 g |
| Core material | ferritic core |
| Varistor protection | built-in varistor |
| Short-circuit protection | built-in |
| High voltage outputs | 2 |
| Output voltage max | 15 kV |
| Low voltage directive | 73/23/EEC |
| Complies with directive | 2004/108/EC |
| Built-in filter | integrated EMC filter |
| Operating principle | high-frequency electronic generator |
| Application scope | domestic, commercial and industrial installations |
| Light weight | light weight |
| High efficiency | high efficiency |
| Mounting and connecting systems | various mounting and connecting systems |
| Protection against temperature fluctuations | special compound |
| Overload protection | special compound |
| Power cable options | built-in power cable or connector |
| Secondary current | 55 mA |
| Duty cycle | 100% |
| Net weight | 0.42 kg |
| Power consumption | low power consumption |
| Frequency | 50–60 Hz |
67.88 EUR
61.71EUR
in stock · 2
incl. 21% VAT · 51.00 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma Ignition transformer 15910752 is a high-frequency electronic generator designed for ignition in gas and liquid fuel burners. It operates with a secondary voltage of 12–12 kV, a secondary current of 55 mA, and a duty cycle of 100%. The transformer features a ferritic core, built-in varistor and short-circuit protection, and an integrated EMC filter, complying with directives 73/23/EEC and 2004/108/EC. It has two high-voltage outputs, a maximum output voltage of 15 kV, and is suitable for domestic, commercial, and industrial installations. The unit weighs approximately 0.42 kg and includes a standard power cable length of 560 mm.
Further details
| Application | gas burners, light and heavy liquid fuel burners |
|---|---|
| Connector availability | all types of connectors available on request |
| IMQ resolution | EN 61558-1:1997 + A1:1998 +A11:2003 and EN 61558-2-3:2000 |
| Single or double-pin high voltage output | single or double-pin high voltage output |
Choosing and fitting
When selecting an ignition transformer of this type, ensure the supply voltage, frequency, and output voltage match the burner's requirements. The transformer must have the correct number of high-voltage outputs and compatible mounting and connecting systems. Check the recommended spark distance and maximum ignition cable length to ensure proper installation. The transformer should be compatible with the burner's controller, and the power cable or connector option must match the existing setup.
Signs of failure
Common failures in ignition transformers include short circuits, open circuits, or breakdown of insulation, leading to weak or no spark. Equipment may fail to ignite, causing burner lockout or repeated ignition attempts. Check for visible damage, measure output voltage with a suitable tester, and verify the spark gap and cable integrity. Overheating or moisture ingress can also cause intermittent operation.
All specifications
| Supply voltage | 50–60 V |
|---|---|
| Secondary voltage | 12–12 kV |
| Poles / outlets | 2 |
| Construction type | high-frequency electronic generator |
| Protection | IP00 |
| Compatible controllers | Brahma controllers |
| Peak current (mA) | 55 mA |
| Output voltage frequency | 12 kHz |
| Protection class (IP) | IP00 |
| Recommended spark distance | 3–5 mm |
| Maximum length of ignition cable with integrated electronic ignition | 1.5 m |
| Standard power cable length | 560 mm |
| Weight (approx) | about 420 g |
| Core material | ferritic core |
| Varistor protection | built-in varistor |
| Short-circuit protection | built-in |
| High voltage outputs | 2 |
| Output voltage max | 15 kV |
| Low voltage directive | 73/23/EEC |
| Complies with directive | 2004/108/EC |
| Built-in filter | integrated EMC filter |
| Operating principle | high-frequency electronic generator |
| Application scope | domestic, commercial and industrial installations |
| Light weight | light weight |
| High efficiency | high efficiency |
| Mounting and connecting systems | various mounting and connecting systems |
| Protection against temperature fluctuations | special compound |
| Overload protection | special compound |
| Power cable options | built-in power cable or connector |
| Secondary current | 55 mA |
| Duty cycle | 100% |
| Net weight | 0.42 kg |
| Power consumption | low power consumption |
| Frequency | 50–60 Hz |
Part numbers
| SKU | 15910752 |
|---|---|
| Additional article | 246.820.073 |