{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Brahma Ignition transformer T13/M 15177061

SKU 15177061 Model T13/M Brand Brahma

Photos

Key specifications

Supply voltage220 V
Secondary voltage8 kV
Poles / outlets1
Length110 mm
Width96 mm
Height78 mm
Body materialPBT with 30% fiberglass
Installation typeany position
Recommended spark distance3–5 mm
Mounting systems varietydifferent mounting systems
Default connection insulatorscrew terminal
Grounding pointsingle grounding center
Protection class (IP)IP00
Input effective current0.65
Dimensions11x9.6x7.8 cm
Weight2000 g
Mounting featureany position
Standard power cable length550 mm
Electrical insulationpolyester resin
Secondary groundinggrounded in the center
RF shield groundingmust be securely grounded
Secondary current16 mA
Duty cycle100%
Net weight2 kg
Power consumption145 W
Frequency50 Hz
all specifications (26) ↓
180.49 EUR
164.08EUR
in stock · 2

incl. 21% VAT · 135.60 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Brahma T13/M ignition transformer (SKU 15177061) is designed for burners operating on liquid or gaseous fuels. It operates with a supply voltage of 220 V at 50 Hz, delivering a secondary voltage of 8 kV and a secondary current of 16 mA. The transformer has a duty cycle of 100%, power consumption of 145 W, and an input effective current of 0.65 A. It features a PBT body with 30% fiberglass, polyester resin insulation, and a single grounding center. The unit measures 110x96x78 mm, weighs 2 kg, and has a protection class of IP00.

Further details

Construction Typemagnetic circuit in the form of a shell
Designationletter T followed by model numbers
Fire Retardant Capstwo caps painted with flame retardant paint
High Voltage Cables Placementavoid placing high voltage cables next to other cables

Choosing and fitting

When selecting a replacement ignition transformer of this type, verify that the supply voltage, frequency, secondary voltage, and secondary current match the burner's requirements. Check the mounting system and dimensions to ensure compatibility with the existing bracket. The connection insulator is typically a screw terminal unless otherwise specified; confirm the high-voltage cable connector type. The transformer can be installed in any position, but the grounding point must be securely connected to the system ground.

Signs of failure

Common failure modes for ignition transformers include shorted or open secondary windings, insulation breakdown, and grounding issues. Symptoms may include weak or no spark at the electrodes, intermittent ignition, or burner lockout. Check the secondary voltage with a suitable probe, inspect for visible damage or burning, and verify that the grounding shield is properly connected.

All specifications

Supply voltage220 V
Secondary voltage8 kV
Poles / outlets1
Length110 mm
Width96 mm
Height78 mm
Body materialPBT with 30% fiberglass
Installation typeany position
Recommended spark distance3–5 mm
Mounting systems varietydifferent mounting systems
Default connection insulatorscrew terminal
Grounding pointsingle grounding center
Protection class (IP)IP00
Input effective current0.65
Dimensions11x9.6x7.8 cm
Weight2000 g
Mounting featureany position
Standard power cable length550 mm
Electrical insulationpolyester resin
Secondary groundinggrounded in the center
RF shield groundingmust be securely grounded
Secondary current16 mA
Duty cycle100%
Net weight2 kg
Power consumption145 W
Frequency50 Hz

Part numbers

SKU15177061
Additional article246.820.060
ModelT13/M