Brahma Ignition transformer TC1SVCAF 15910500
SKU 15910500
Model TC1SVCAF
Brand Brahma
Photos
Key specifications
| Supply voltage | 110-120 V 50/60 Hz |
|---|---|
| Secondary voltage | 15 kV |
| Poles / outlets | 1 |
| Maximum length of ignition cable with integrated electronic ignition | 1.5 m |
| Peak current (mA) | 45 mA |
| Rated current (mA) | 20 mA |
| Recommended spark distance | 3–5 mm |
| Standard power cable length | 560 mm |
| Output voltage frequency | 6 kHz |
| Ingress protection | IP00 |
| Core material | ferritic |
| Short-circuit protection | built-in |
| Complies with directive | 2004/108/ec |
| External filter not required | yes |
| Mounting screw | M4x45 screws |
| Compatible components | Brahma controllers |
| High efficiency | high efficiency and ignition power |
| Compact size | compact size |
| Light weight | light weight |
| Mounting and connecting systems | various fastening and connecting systems |
| Weight | about 420 |
| Secondary current | 20 mA |
| Duty cycle | 50 |
| Net weight | 0.42 kg |
| Power consumption | low power consumption |
| Frequency | 50–60 Hz |
67.88 EUR
61.71EUR
in stock · 2
incl. 21% VAT · 51.00 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma TC1SVCAF ignition transformer, SKU 15910500, is a compact device used in gas and liquid fuel burners for domestic, commercial, and industrial applications. It operates on a supply voltage of 110-120 V at 50/60 Hz and generates a secondary voltage of 15 kV with a rated current of 20 mA. The transformer features a ferritic core, built-in short circuit protection, and complies with directive 2004/108/EC without requiring an external filter. It has a duty cycle of 50%, a peak current of 45 mA, and a recommended spark distance of 3-5 mm. The unit weighs approximately 0.42 kg and includes a standard power cable length of 560 mm, with a maximum ignition cable length of 1.5 m.
Further details
| Application | gas and liquid fuel burners for domestic, commercial and industrial use |
|---|---|
| Connector options | all types of connectors, including cable options, can be ordered on request |
| Construction type | high-frequency electronic generator with ferritic core transformer |
| Electromagnetic interference protection | available with filter to reduce electromagnetic interference |
| Overload protection | special compound with high thermal conductivity and expansion coefficient |
| Protection against temperature fluctuations | special compound with high thermal conductivity and expansion coefficient |
| Single or double contact | single or double-contact high voltage output |
| Thermal compound | special compound with high thermal conductivity and expansion coefficient |
| Varistor protection | built-in varistor protects against power surges |
Choosing and fitting
When selecting an ignition transformer of this type, ensure the supply voltage and frequency match the burner's electrical system. The mounting configuration, including the number of poles and screw type (e.g., M4x45), must align with the controller and burner design. Verify the high-voltage output connection type (threaded or Ø4 mm connector) and the required ignition cable length. Compatibility with the burner's controller is essential, as the transformer is designed to be used with specific controllers.
Signs of failure
Common failures in ignition transformers of this kind include short circuits or open circuits in the high-voltage output, leading to weak or absent sparks. Overheating or insulation breakdown may cause intermittent ignition or complete failure. Check for visible damage, measure the secondary voltage with a suitable probe, and inspect the spark electrodes for proper gap and condition.
All specifications
| Supply voltage | 110-120 V 50/60 Hz |
|---|---|
| Secondary voltage | 15 kV |
| Poles / outlets | 1 |
| Maximum length of ignition cable with integrated electronic ignition | 1.5 m |
| Peak current (mA) | 45 mA |
| Rated current (mA) | 20 mA |
| Recommended spark distance | 3–5 mm |
| Standard power cable length | 560 mm |
| Output voltage frequency | 6 kHz |
| Ingress protection | IP00 |
| Core material | ferritic |
| Short-circuit protection | built-in |
| Complies with directive | 2004/108/ec |
| External filter not required | yes |
| Mounting screw | M4x45 screws |
| Compatible components | Brahma controllers |
| High efficiency | high efficiency and ignition power |
| Compact size | compact size |
| Light weight | light weight |
| Mounting and connecting systems | various fastening and connecting systems |
| Weight | about 420 |
| Secondary current | 20 mA |
| Duty cycle | 50 |
| Net weight | 0.42 kg |
| Power consumption | low power consumption |
| Frequency | 50–60 Hz |
Part numbers
| SKU | 15910500 |
|---|---|
| Additional article | 246.820.042 |
| Model | TC1SVCAF |