Brahma Ignition transformer TCD1FAV 15930023
SKU 15930023
Model TCD1FAV
Brand Brahma
Photos
Key specifications
| Supply voltage | 230 V |
|---|---|
| Secondary voltage | 6 kV |
| Poles / outlets | 1 |
| Single or double-pin high voltage output | single or double-pin |
| Mounting and connecting systems | various |
| Short-circuit protection | built-in |
| Operating principle | high-frequency electronic generator |
| Ferritic core | yes |
| Maximum length of ignition cable with integrated electronic ignition | 1.5 m |
| Recommended spark distance | 3–5 mm |
| Peak current (mA) | 83 mA |
| Protection | IP 00 |
| Built-in filter | yes |
| Dimensional series compatibility | TC and TD series |
| High efficiency | yes |
| Varistor protection | built-in varistor |
| Connector availability | available on request |
| Complies with directive | 2004/108/EC |
| Low voltage directive | 2006/95/EC |
| IMQ resolution | EN 61558-1:2005+A1:2009 and EN 61558-2-3:2010 |
| Output voltage frequency | 13 kHz |
| Protection against temperature fluctuations | special composition |
| Compact design | extremely compact overall dimensions |
| Secondary current | 37 mA |
| Duty cycle | 33% |
| Net weight | 0.25 kg |
| Power consumption | yes |
| Frequency | 50 Hz |
—price on request
on order
shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Brahma Ignition transformer TCD1FAV (SKU 15930023) is a high-frequency electronic generator with a ferritic core, designed for gas and liquid fuel burners. It operates at a supply voltage of 230 V and 50 Hz, producing a secondary voltage of 6 kV with a secondary current of 37 mA. The transformer features a built-in short circuit protection, varistor protection, and an integrated filter, complying with directives 2004/108/EC and 2006/95/EC. It has a duty cycle of 33%, a peak current of 83 mA, and an output voltage frequency of 13 kHz. The device is compact, weighs 0.25 kg, and is compatible with Brahma TC and TD series, with a maximum ignition cable length of 1.5 m and a recommended spark distance of 3–5 mm.
Further details
| Application scope | gas burners, burners for light and heavy liquid fuels in domestic, commercial, industrial installations |
|---|---|
| Connector options | triangular connector SP1 or connector 6.35x0.8 |
| Interchangeability | replace most transformers from other manufacturers |
| Thermal compound | special composition with high thermal conductivity and special expansion coefficient |
Choosing and fitting
When selecting an ignition transformer of this type, ensure the supply voltage, frequency, and secondary voltage match the burner's requirements. The mounting and connecting systems vary, so verify the physical dimensions and connector type (e.g., single or double-pin) against the existing unit. The transformer's dimensions are compatible with TC and TD series, but always compare the mounting holes and high-voltage output configuration. The ignition cable length and spark distance must be within the specified limits for proper operation.
Signs of failure
Typical failures of ignition transformers include short circuits, open circuits, or breakdown of the high-voltage insulation, often caused by moisture, overheating, or voltage surges. Symptoms on the equipment include no spark at the electrode, weak or intermittent sparking, or burner ignition failure. Check the primary and secondary circuits for continuity, inspect the high-voltage cable and connections for damage, and verify the spark gap is within the recommended range. If the transformer overheats or trips, inspect the duty cycle and ensure the cooling is adequate.
Fits equipment
Brahma TC and TD series
All specifications
| Supply voltage | 230 V |
|---|---|
| Secondary voltage | 6 kV |
| Poles / outlets | 1 |
| Single or double-pin high voltage output | single or double-pin |
| Mounting and connecting systems | various |
| Short-circuit protection | built-in |
| Operating principle | high-frequency electronic generator |
| Ferritic core | yes |
| Maximum length of ignition cable with integrated electronic ignition | 1.5 m |
| Recommended spark distance | 3–5 mm |
| Peak current (mA) | 83 mA |
| Protection | IP 00 |
| Built-in filter | yes |
| Dimensional series compatibility | TC and TD series |
| High efficiency | yes |
| Varistor protection | built-in varistor |
| Connector availability | available on request |
| Complies with directive | 2004/108/EC |
| Low voltage directive | 2006/95/EC |
| IMQ resolution | EN 61558-1:2005+A1:2009 and EN 61558-2-3:2010 |
| Output voltage frequency | 13 kHz |
| Protection against temperature fluctuations | special composition |
| Compact design | extremely compact overall dimensions |
| Secondary current | 37 mA |
| Duty cycle | 33% |
| Net weight | 0.25 kg |
| Power consumption | yes |
| Frequency | 50 Hz |
Part numbers
| SKU | 15930023 |
|---|---|
| Additional article | 246.820.055 |
| Model | TCD1FAV |