| Supply voltage | 230 V |
|---|---|
| Secondary voltage | 8 kV |
| Output type | 1x8 kV |
| Housing type | compact housing |
| Application scope | gas and dual-fuel burners |
| Operating phase | only during ignition period |
| Ignition cable insulation | silicone-insulated |
| Working with | ignition electrode and burner control |
| Frequency | 50 Hz |
| Country of origin | Italy |
87.40 EUR
79.45EUR
in stock · 2
incl. 21% VAT · 65.66 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
The Cofi TRE820P is a single-pole ignition transformer with a supply voltage of 230 V and a secondary voltage of 8 kV, operating at 50 Hz. It is designed for gas and dual-fuel burners, providing a high-voltage discharge to the ignition electrode during the ignition period. This transformer is housed in a compact enclosure and is compatible with burners from COFI, CIB Unigas, Riello, Ecoflam, and other brands. It is an OEM equivalent to the FIDA Compact 8/20PM P.
Further details
| Advantages | powerful ignition, compact and durable housing, high reliability, easy installation |
|---|---|
| Application | gas burners, industrial and domestic boiler houses, heat guns, dryers, baking and process equipment |
| Cable condition | hardened or cracked cable can leak spark to earth |
| Compatibility check | match primary voltage and duty cycle, check cable and terminal pattern |
| Replacement | replacement of analogue fida compact 8/20pm p |
| Safety time | if flame not confirmed within safety time, control locks out |
Choosing and fitting
When selecting an ignition transformer of this type, verify that the primary voltage (e.g., 230 V) and frequency match the burner's supply, and that the secondary voltage and current rating are appropriate for the electrode gap. Check the mounting dimensions, terminal types, and high-voltage cable connector pattern to ensure compatibility with the existing wiring and electrode assembly. The transformer operates only during the ignition sequence, so the duty cycle must align with the burner control's safety time.
Signs of failure
Typical failures include no spark at the electrode, intermittent ignition, or a spark that leaks to ground due to cracked or hardened ignition cables. The burner may fail to light or lock out after the safety time if the transformer does not produce sufficient voltage. Check the transformer's primary voltage and secondary output with a suitable meter, and inspect the ignition cable for insulation damage before replacing the unit.
Fits equipment
multiple COFI, CIB Unigas, Riello, Ecoflam and many other brands of gas burnersCofi TRE820PCIB Unigas Riello Ecoflam
All specifications
| Supply voltage | 230 V |
|---|---|
| Secondary voltage | 8 kV |
| Output type | 1x8 kV |
| Housing type | compact housing |
| Application scope | gas and dual-fuel burners |
| Operating phase | only during ignition period |
| Ignition cable insulation | silicone-insulated |
| Working with | ignition electrode and burner control |
| Frequency | 50 Hz |
| Country of origin | Italy |
Part numbers
| SKU | TRE820P |
|---|---|
| Additional article | 309.820.015 |
| OEM equivalent | FIDA Compact 8/20PM P |