{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Kromschroder Ignition transformer TGI7-25/20W 84391080

SKU 84391080 Model TGI7-25/20W Brand Kromschroder

Photos

no photo yet

Key specifications

Supply voltage230 V
Secondary voltage7 kV
Ingress protectionIP65
Single electrode operationyes
Secondary current25 mA
Duty cycle20%
Frequency50 Hz
all specifications (7) ↓
564.08 EUR
512.80EUR
in stock · 1

incl. 21% VAT · 423.80 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder TGI7-25/20W ignition transformer (SKU 84391080) is designed for high-voltage spark ignition of gas burners and gas-ignited or directly ignited oil burners. It operates with a supply voltage of 230 V at 50 Hz, providing a secondary voltage of 7 kV and a secondary current of 25 mA. The transformer has a duty cycle of 20% and an ingress protection rating of IP65. It supports single-electrode operation, where ignition and ionization currents flow over a common electrode. This unit must be mounted in a housing, such as a control cabinet.

Further details

Output current25 mA at 50 Hz

Choosing and fitting

Ignition transformers of this type are selected by matching the supply voltage, secondary voltage, and secondary current to the burner's ignition system requirements. The duty cycle must be compatible with the burner's operational cycle to prevent overheating. Installation requires mounting in a suitable enclosure that meets the specified ingress protection rating, and the transformer must be connected according to the manufacturer's wiring diagram. Ensure the electrode configuration (single or dual) matches the transformer's capability.

Signs of failure

Common failure modes for ignition transformers include internal short circuits, open windings, or insulation breakdown, leading to weak or absent spark. Symptoms may include the burner failing to ignite, intermittent ignition, or a buzzing sound from the transformer. Check for visible damage, measure primary and secondary voltages with appropriate safety precautions, and verify the duty cycle is not exceeded.

All specifications

Supply voltage230 V
Secondary voltage7 kV
Ingress protectionIP65
Single electrode operationyes
Secondary current25 mA
Duty cycle20%
Frequency50 Hz

Part numbers

SKU84391080
Additional article624.820.016
ModelTGI7-25/20W