Kromschroder Ignition transformer TZI 8-12/100QE 84391130

SKU 84391130 Model TZI 8-12/100QE Brand Kromschroder

Photos

no photo yet

Key specifications

Secondary voltage8 kV
Poles / outlets1
Protection class (IP)IP00
Secondary insulationgrounded pole
Installation typecabinet installation
Ignition cable insulationsilicone-insulated
Operating phaseignition phase only
Operating modecontinuous
Secondary current9–12 mA
Duty cycle100%
Frequency50–60 Hz
all specifications (11) ↓
320.39 EUR
291.26EUR
in stock · 2

incl. 21% VAT · 240.71 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Kromschroder TZI 8-12/100QE is an ignition transformer designed for industrial burners, converting supply voltage into a high-voltage discharge of 8 kV with a secondary current of 9–12 mA. It operates at a frequency of 50–60 Hz and has a 100% duty cycle, allowing continuous operation. This single-pole transformer features grounded secondary insulation and is intended for cabinet installation with IP00 protection. It is energized only during the ignition phase, as controlled by the burner management system.

Choosing and fitting

When selecting a replacement ignition transformer of this type, verify that the secondary voltage and current match the electrode gap design, and that the primary voltage corresponds to the burner's mains supply. The duty cycle must be adequate for the control sequence, and the terminal pattern and cable connector must be compatible with existing wiring. Mounting forms include cabinet installation, and the high-voltage cable must be silicone-insulated to withstand heat and electrical stress.

Signs of failure

Typical failures of ignition transformers include internal short circuits or open windings, leading to weak or absent spark. The burner may fail to ignite or experience intermittent ignition, often accompanied by a buzzing sound from the transformer. Check the high-voltage cable for hardening or cracks, as these can leak the spark to earth, mimicking a faulty transformer. Also inspect the electrode gap and insulation for wear or contamination.

All specifications

Secondary voltage8 kV
Poles / outlets1
Protection class (IP)IP00
Secondary insulationgrounded pole
Installation typecabinet installation
Ignition cable insulationsilicone-insulated
Operating phaseignition phase only
Operating modecontinuous
Secondary current9–12 mA
Duty cycle100%
Frequency50–60 Hz

Part numbers

SKU84391130
Additional article624.820.035
ModelTZI 8-12/100QE