Brahma Uv cell 18210068

SKU 18210068 Brand Brahma

Photos

Key specifications

Mounting thread sizemust match the existing installation
Sight tube lengthmust match the existing installation
Wiring polarityverify the wiring polarity
Operating voltageverify the cell's operating voltage
all specifications (4) ↓
215.62 EUR
196.02EUR
in stock · 3

incl. 21% VAT · 162.00 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

Brahma UV cell 18210068 is a flame detector that responds to ultraviolet radiation emitted by flames, used in gas and oil burner flame-proving circuits. It is compatible with Brahma 18210068 and Sylvania P630. 88 models. The cell is designed for precise control of gas burner valves, providing opening and closing when voltage is applied, with high thermal resistance and durable insulation. Its design resists vibrations and mechanical loads. The cell is typically mounted on a flame-sight tube or directly on the burner housing, aimed at the combustion zone.

Further details

Compatibility with burner controlmatching the signal type, not just the physical fit
Installation requirementensure the power is off and the burner control is safe to work on; check sight path is clear of soot, carbon, or oil deposits; align the cell to see the steady flame, not the spark or a reflected source
Operating Principleresponds to ultraviolet radiation emitted by the flame
Operating lifefinite operating life; sensitivity may degrade over time

Choosing and fitting

When selecting a UV cell for replacement, key parameters include spectral sensitivity range (typically 190–290 nm), response time, supply voltage, and output signal type (current or voltage pulse). The physical mounting-thread size, sight tube length, and connector or flying leads must match the existing installation; an incorrect fit can cause false readings or no flame signal. Ensure the sight path is clear of soot, carbon, or oil deposits, and align the cell to see the steady flame, not the spark or reflected source. Verify wiring polarity and operating voltage against the burner control's requirements.

Signs of failure

UV cells have a finite operating life; sensitivity may degrade over time due to solarisation of the quartz window or contamination by combustion residues. Symptoms include burner lockout during start-up or loss of flame signal during operation. A dirty lens can mimic a failing cell, so check and clean the sight path. If lockout occurs after replacement, verify wiring polarity, operating voltage, and compatibility with the burner control.

Fits equipment

Brahma 18210068Sylvania P630.88

All specifications

Mounting thread sizemust match the existing installation
Sight tube lengthmust match the existing installation
Wiring polarityverify the wiring polarity
Operating voltageverify the cell's operating voltage

Part numbers

SKU18210068
Additional article920.973.004