Description

The Honeywell UV detector minipeeper C7027A1064/U is an industrial flame sensor that detects ultraviolet radiation emitted by flames. It is designed for use with Honeywell flame monitoring systems in gas, oil, and combined burners. This model is compatible with amplifiers R7249A, R7290A, R7749B, and R7849A. It can operate at pressures up to 5 psi and includes a flange seal and UV reading tubes. The sensor is compact, suitable for installation on purge pipes, and features two 6-foot color-coded wires for electrical connections.

Further details

Electrical connectionstwo 6-foot-long [1.83 m] color-coded wires conforming to nec class 1
Wire length 24 ftone model comes with 24-foot-long [7.32 m] wires

Choosing and fitting

When selecting a replacement UV detector of this type, ensure compatibility with the burner's flame monitoring amplifier model. Verify the mounting configuration, as these sensors are often installed on purge pipes with a flange seal. Check the pressure rating to confirm it meets the system's requirements. Electrical connections typically include two color-coded wires; confirm the wire length and type match the existing setup.

Signs of failure

UV detectors of this kind may fail due to contamination or degradation of the sensing tube, leading to intermittent or loss of flame detection. Symptoms include burner shutdowns or failure to ignite, often accompanied by a fault code on the control system. Check the sensor's window for dirt or damage, and verify the wiring connections are secure.

Fits equipment

Honeywell R7249A

All specifications

Detection principleUV detector
Detection principleultraviolet radiation detection
Catalogue article numbers534.211.017
Flange sealincluded
UV reading tubesincluded
Maximum pressure5 psi

Part numbers

SKUC7027A1064/U
Additional article534.211.017
OEM equivalentR7249A
OEM equivalentR7290A
OEM equivalentR7749B
OEM equivalentR7849A