{# Разметка для пересылки ссылки. Заголовок и описание по умолчанию берутся из тех же блоков, что и обычные: раньше на каталоге, разделах и карточках тут стояло голое «kroms» и пустое описание. #}

Honeywell Industrial flame sensor C7035A1023/U

SKU C7035A1023/U Brand Honeywell

Photos

Key specifications

Detection principleUV sensor
Connection thread1/2-14 NPSM
Detection principleultraviolet radiation
Wire length options6 ft [1.83 m]
Flame detectionend of flame
Catalogue article numbers534.211.043
Housing standardNEMA type 4 and 4X
UV reading tube installationreplaced in the field
all specifications (8) ↓
479.16 EUR
435.60EUR
in stock · 1

incl. 21% VAT · 360.00 EUR excl. VAT · shipping calculated at checkout

  • Worldwide shipping from stock
  • Original manufacturer part
  • Dispatch within 24 h for stocked items

Description

The Honeywell C7035A1023/U is an industrial flame sensor that detects the presence of ultraviolet radiation emitted by a flame. It is used with Honeywell flame monitoring systems for gas, oil, and combined burners. The sensor features a UV detection tube, a 1/2-14 NPSM connection thread, and a 6 ft [1.83 m] wire length. Its housing meets NEMA type 4 and 4X standards, and the UV reading tube is replaceable in the field. Compatible with R7249A, R7290A, R7749B, and R7849A amplifiers.

Further details

CertificationUL MP268, CSA LR 95329-1, FM, Industrial Risk Insurers
Installation requirementsdetector must be in direct line of sight of flame and not exposed to other UV radiation
Parallel connection notetwo flame detectors can be connected in parallel in cases where flame reading is difficult

Choosing and fitting

When selecting a replacement flame sensor of this type, ensure the detector type (UV sensor) and detection principle (ultraviolet radiation) match the burner control system. The connection thread (e.g., 1/2-14 NPSM) must fit the mounting, and the wire length must be sufficient for the installation. Verify the housing standard (e.g., NEMA type 4/4X) meets environmental requirements. The UV reading tube should be compatible with the amplifier model.

Signs of failure

Typical failures include a faulty UV tube, which may cause the burner to shut down or fail to ignite. Symptoms include intermittent flame detection or a false flame signal. Check the UV tube for damage or contamination, and verify the sensor's line of sight to the flame is unobstructed.

All specifications

Detection principleUV sensor
Connection thread1/2-14 NPSM
Detection principleultraviolet radiation
Wire length options6 ft [1.83 m]
Flame detectionend of flame
Catalogue article numbers534.211.043
Housing standardNEMA type 4 and 4X
UV reading tube installationreplaced in the field

Part numbers

SKUC7035A1023/U
Additional article534.211.043
Type designationR7249A
Type designationR7290A
Type designationR7749B
Type designationR7849A
Type designation129808
Type designationC7035A1064