Kromschroder Gas pressure switch DG 40VCT6-6W 84448840
SKU 84448840
Model DG 40VCT6-6W
Brand Kromschroder
Photos
Key specifications
| Setting range | 0.03–0.17 mbar |
|---|---|
| Control features | hand wheel adjustment on housing |
| Design features | replaceable microswitch with change-over contact |
| Wire length | 18 |
| Contact rating | 6(2)A 250V |
| Application | burner and boiler systems |
165.72 EUR
150.65EUR
in stock · 2
incl. 21% VAT · 124.50 EUR excl. VAT · shipping calculated at checkout
- Worldwide shipping from stock
- Original manufacturer part
- Dispatch within 24 h for stocked items
Description
This gas pressure switch from Kromschroder is used in burner and boiler systems. It has a pressure range of 0.03–0.17 mbar and a contact rating of 6(2)A 250V. The setpoint is adjusted with a hand wheel on the housing. The switch has a replaceable microswitch with change-over contact and an 18-inch wire length. Model DG 40VCT6-6W, SKU 84448840.
Further details
| Adjustment method | hand wheel directly on the housing |
|---|---|
| Connection type | 4-pin connector with socket and 18" wires |
| Electrical connection | standard 4-pin connector with socket and 18" wires |
| Function | monitors gas pressure downstream of gas valve or at burner manifold |
| Gas type | natural gas, lpg, biogas, exhaust gases, air |
| Media compatibility | gas and air (natural gas, LPG, biogas, exhaust gases) |
| Monitoring location | downstream of gas valve or at burner manifold |
Choosing and fitting
Parts of this type are selected by the medium (gas), the switching range and differential, the type of connection (thread or hose spigot), and the contact rating. Before ordering, compare the setpoint range and connection geometry with the existing installation. The differential, or the gap between the setpoint and reset point, must suit the system to avoid unnecessary lockouts.
Signs of failure
Common failure modes for this type include a torn diaphragm, a blocked impulse tube, or a drifted setpoint. These faults often produce lockouts that can be mistaken for ignition problems. Checking the pressure switch, its impulse line, and the setpoint should be part of systematic diagnostics.
All specifications
| Setting range | 0.03–0.17 mbar |
|---|---|
| Control features | hand wheel adjustment on housing |
| Design features | replaceable microswitch with change-over contact |
| Wire length | 18 |
| Contact rating | 6(2)A 250V |
| Application | burner and boiler systems |
Part numbers
| SKU | 84448840 |
|---|---|
| Additional article | 624.214.273 |
| Model | DG 40VCT6-6W |